7 Before Programming
7.4 General Rules for Applied Instructions
45
FX
3U
-CF-ADP User's Manual
1
Introduc
tion
2
S
pecifi
cation
3
Sy
stem
 
Configurati
o
n
4
Ins
tal
lation
5
Wi
rin
g
6
Functi
o
n
s
7
Bef
o
re
 
Programm
ing
8
C
F
-AD
P
 Appl
ied 
Ins
tructi
ons
 
Explanati
o
n
9
Program 
Examples
10
T
roubl
esho
oti
n
g
2) To use at a position other than just below the CF-ADP instructions.
If two or more CF-ADP instructions are used in a program, the "Instruction execution complete" flag
(M8029) and "Instruction execution abnormal end" flag (M8329) will be turned on or off after execution of
each instruction.
If it is necessary to use the "Instruction execution complete" flag (M8029) or "Instruction execution
abnormal end" flag (M8329) at a point other than just below the instruction, turn on or off another bit
device just below the instruction, and use the contact as the command contact.
M8000
FNC 72
DSW
X10
Y10
D0
K1
FNC 22
MUL
D0
K10
D20
M8029
Completion
 of instruction
execution
M0
FNC300
FLCRT
K1
D0
D10
M8029
Completion
of instruction
execution
Switches "instruction
execution complete"
flag of the DSW
instruction from M8029
to M100.
M100
M200
Switches the
"instruction execution
complete" flag of the
FLCRT instruction from
M8029 to M200.
M100
Functions as the instruction
execution complete flag of
the DSW instruction.
RST
M0
M200
Functions as the instruction
execution complete flag of the
FLCRT instruction.
Y000
K1