6 - 51 
MELSEC-A
6   SEQUENCE PROGRAM USED FOR POSITIONING CONTROL 
 
6.6 Program details 
6.6.1 Initialization program 
(1)   Zero point return request OFF program 
This program forcibly turns OFF the "zero point return request flag" (RX(n+1)F, 
RX(n+4)F) which is ON. 
When using a system that does not require zero point return, assemble the 
program to cancel the "zero point return request" made by the D75P2 when the 
power is turned ON, etc. 
 
 Data requiring setting 
 
Set the following data to use the zero point return flag OFF request. 
 
Setting item 
Setting 
value 
Setting details 
Remote input/output 
Axis 1 
Axis 2 
Zero point return request 
flag OFF request 
ON 
Set to "ON: Turn zero point return request flag 
OFF". 
RY(n+2)A RY(n+4)A
 
                 *  Refer to section "3.4 Specifications of input/output signals for master module" for details on the setting details. 
 
 Time chart for zero point return OFF request 
 
Remote station READY signal
D75P2 READY signal 
OFF
ON
ON
Zero point return request flag
Zero point return request flag OFF request
OFF
OFF
 [RX(n+7)B]
[RXn0]
OFF
ON
[RX(n+1)F, RX(n+4)F]
[RY(n+2)A, RY(n+4)A]
ON
 
 
Fig. 6.1 Time chart for zero point return OFF request 
 
 
(2)   External start function valid setting program 
This program is used to validate the "external signal" beforehand when using the 
external start function (external start, speed change, skip). (Set which function to 
use beforehand in " Pr.43
 External start function selection".) 
Set the following data to validate the "external signal". 
 
Setting item 
Setting 
value 
Setting details 
Remote input/output 
Axis 1 
Axis 2 
External start valid 
ON 
Set to "ON: Validate external start". 
RY(n+2)B  RY(n+4)B
 
                 *  Refer to section "3.4 Specifications of input/output signals for master module" for details on the setting details.