11   MANUAL CONTROL 
 
11.3 Manual pulse generator operation 
11.3.1 Outline of manual pulse generator operation 
Important 
 
Create the sequence program so that "Manual pulse generator enable flag 
(RY(n+2)9, RY(n+4)9)" is always set to "0" (disabled) when a manual pulse 
generator operation is not carried out. 
 *  Mistakenly touching the manual pulse generator when the manual pulse 
generator enable flag is set to "1" (enable) can cause accidents or incorrect 
positioning. 
 
 Manual pulse generator operation 
 
In manual pulse generator operations, pulses are input to the D75P2 from the 
manual pulse generator. This causes the same No. of input pulses to be output 
from the D75P2 to the servo amplifier, and the workpiece is moved in the 
designated direction.  
The following shows and example of manual pulse generator operation.  
 
1) 
When the "Manual pulse generator enable flag (RY(n+2)9, RY(n+4)9)" is set to "1", the 
BUSY signal turns ON and the manual pulse generator operation is enabled. 
2) 
The workpiece is moved corresponding to the No. of pulses input from the manual pulse 
generator. 
3) 
The workpiece movement stops when no more pulses are input from the manual pulse 
generator. 
4) 
When the "Manual pulse generator enable flag (RY(n+2)9, RY(n+4)9)" is set to "0", the 
BUSY signal turns OFF and the manual pulse generator operation is disabled. 
 
Manual pulse 
generator 
operation stops
t
BUSY signal
                   [RXn4, RXn5]
Manual pulse 
generator input
Positioning start complete
signal           
Manual pulse generator operation enabled
OFF
ON
OFF
1) 2)
3)
4)
Manual pulse generator 
enable flag
*
1
*
2
      [RY(n+2)9, RY(n+4)9]
[RXn1, RXn2]
OFF
ON
 
 [Precautions] 
  *
  When the input from the manual pulse generator stops, the last pulse will be output from the 
D75P2, delayed by the time for one control cycle (180ms).  
  *
  The start complete signal does not turn ON in manual pulse generator operation. 
Fig. 11.11 Manual pulse generator operation