13 - 3 
MELSEC-A
13   COMMON FUNCTIONS 
 
13.2 Parameter initialization function 
POINT 
 
It is recommended to use the AD75 software package to execute this function. 
 
"The parameter initialization function" is used to return the setting data set in the 
D75P2 flash ROM and OS memory to their factory-set initial values.   
This function is used when several parameter errors occur and the D75P2 will not start. 
In this case, resetting is carried out after the setting data are initialized. (If there is an 
abnormality in the parameters set in the D75P2 when the remote station READY signal 
[RX(n+7)B] is turned ON, the D75P2 READY signal [RXn0] will not turn OFF, and 
control will not be possible.) 
Parameter initialization is carried out using one of the following methods.   
 
  Method using the sequence program. 
 
  Method using the AD75 software package.   
 
"The execution method using the sequence program" is explained in this section.   
Refer to the AD75 Software Package Operating Manual for details on the execution 
method using the AD75 software package. 
 
The details shown below explain about the "parameter initialization function".   
   (1) Control details 
   (2) Precautions during control 
   (3) Initializing the parameters 
 
 
(1)   Control details 
The following table shows the setting data initialized by the "parameter 
initialization function".   
(Initialized are "flash ROM" and "OS memory" following data.)   
 
Setting data 
Basic parameters (
Pr.1  to  Pr.11  ) 
Detailed parameters ( Pr.12  to  Pr.44  ) 
Zero point return basic parameters ( Pr.45  to  Pr.50  ) 
Zero point return detailed parameters ( Pr.51  to  Pr.58  ) 
Positioning data 
Start block data 
Condition data