14   TROUBLESHOOTING 
 
14.3 List of errors 
Description of the errors and remedies are shown below. 
 
Division of 
error 
Error 
code 
Error name 
Description 
Action at occurrence of error 
 
 
 
 
 000 
(Normal) 
 
 
 
Fatal error 
001 Fault 
Hardware error 
The system is stopped. 
 
003  Division by zero 
004 Overflow 
005 Underflow 
Error at 
selection of 
stepping 
motor mode 
051 
Outside position 
command range 
 The position data in the parameter is out of 
the setting range for the stepping motor 
mode. 
 The positioning address or movement 
amount setting in the positioning data is out of 
the setting range for the stepping motor 
mode. 
 The D75P2 READY signal (RXn0) does not 
turn OFF. 
 Failure to start. 
 
 
 
 
 
 
 
 
 
 
052 
Outside speed 
command range 
 The speed data in the parameter is out of the 
setting range for the stepping motor mode. 
 The command speed setting in the 
positioning data is out of the setting range for 
the stepping motor mode. 
 The D75P2 READY signal (RXn0) does not 
turn OFF. 
 Failure to start. 
 
 
 
 
 
 
Common 
100 
Peripheral device 
stop during 
operation 
A stop command is supplied during operation 
from a peripheral device. 
Stopping according to the sudden stop 
(stopping group 2) setting (deceleration and 
stop/sudden stop) selected in detail parameter 
2 (However, deceleration and stop only during 
manual pulse generator operation) 
 
101 
Remote station 
READY OFF 
during operation 
The remote station READY signal [RX(n+7)B] 
is turned OFF during operation. 
Stopping according to sudden stop (stopping 
group 2) setting (deceleration and stop/sudden 
stop) selected in detail parameter 2 
(However, deceleration and stop only during 
manual pulse generator operation) 
 
102 
Drive unit 
READY OFF 
The “Drive unit READY” signal is turned OFF 
during operation. 
Immediate stop.