MDS-D-SVJ3/SPJ3 Series Specifications Manual
6-2 Selection of circuit protector and contactor
6-2-2 Selection of contactor
Select the contactor selection current that is calculated from the rated output and the nominal input voltage of the 
drive unit as in the expression below. And then select the contactor whose conventional free-air thermal current 
meets the contactor selection current.
Contactor selection current [A]= 
(Contactor selection current for 200V input [A] / Nominal input voltage [V]) × 200 [V]
Selection of contactor for 200V input
Option part: A contactor is not prepared as an NC unit accessory, so purchase the part from your dealer, etc.
Unit type
MDS-D-SVJ3-
03NA
04NA
07NA
10NA
20NA
35NA
Rated output
0.3kW
0.4kW
0.75kW
1.0kW
2.0kW
3.5kW
Contactor selection 
current for 200V input
2.5A
5A
7A
8A
10A
15A
Selection example of contactor
(Mitsubishi Electric Corp.)
S-N12
-AC200V
S-N12
-AC200V
S-N12
-AC200V
S-N12
-AC200V
S-N18
-AC200V
S-N20
-AC200V
Conventional freeair thermal 
current of the selection example of 
contactor
20A
20A
20A
20A
25A
32A
Unit type
MDS-D-SPJ3-
075NA
22NA
37NA
55NA
75NA
110NA
Rated output
0.75kW
2.2kW
3.7kW
5.5kW
7.5kW
11kW
Contactor selection
current for 200V input
6A
9A
15A
23A
31A
45A
Selection example of contactor
(Mitsubishi Electric Corp.)
S-N12-
AC200V
S-N18-
AC200V
S-N20-
AC200V
S-N25-
AC200V
S-N25-
AC200V
S-N35-
AC200V
Conventional freeair thermal 
current of the selection example of 
contactor
20A
25A
32A
50A
50A
60A
1. Use an alternating contactor.
2. Select a contactor whose excitation coil does not operate at 15mA or less.
 
POINT