Roberts Gorden 350 ユーザーズマニュアル

ページ / 62
SECTION 15: R
EPLACEMENT
 P
ARTS
41 of 51
15.2 Burner Compartment
15.2.1 Burner Injectors
Remove flexible
air duct from spigot 
Remove
access plate
Remove screws and
pull off burner 
compartment cover
Viewing port
for flame probe 
Viewing port
for ignition electrode 
Flame Probe 
Burner
Compartment
Cover 
Rubber Seal
Ignition Electrode 
The burner compartment is 
a sealed compartment. 
Following any work, 
re-seal the compartment 
with the gas pipe rubber 
seal fully in place and all 
screws fitted and tight.
NOTE: Flexible duct only applies 
            for model UHAS.
MODEL
UHA[X][S]
150
UHA[X][S]
175
UHA[X][S]
200
UHA[X][S]
225
UHA[X][S]
250
UHA[X][S]
300
UHA[X][S]
350
UHA[X][S]
400
Orifice Quantity
7
8
9
10
11
12
14
14
Natural Gas (G20)
Orifice Marking
43
43
2.25 mm
2.25 mm
2.25 mm
40
40
40
P/N
91930043
91930043
91930225
91930225
91930225
91930040
91930040
91930040
Propane (G31)
Orifice Marking
1.35 mm
1.35 mm
54
54
54
1.45 mm
53
53
P/N
91930135
91930135
91930054
91930054
91930054
91930145
91930053
91930053
Ensure gas tight fitting of injectors.
Ensure correct alignment with burners.
Ensure all pipe joints are gas tight.