Impinger II – Advantage Digital Service Manual - Domestic 
SEQUENCE OF OPERATION 
IMPINGER II ADVANTAGE 
SERIAL NUMBER 2038616 AND ABOVE 
(OVENS WITH PUSH BUTTON CONTROLS) 
 
MODEL 1116-000-A 
NAT. GAS 
120VAC 
60 HZ.  1 PHASE 
MODEL 1117-000-A 
LP GAS 
120VAC 
60 HZ.  1 PHASE
 
 
POWER SUPPLY 
Electrical power is supplied to the oven by a three-conductor cordset. Voltage 
from the black conductor to the white conductor is 120VAC.  
Black conductor is hot  
White conductor is neutral. 
Green conductor is ground. 
CONTROL BOX AUTO     
COOL DOWN 
When the temperature in the control box reaches 120
°F ± 3° (48.9°C ± 1.7°), 
the cooling fan thermostat will switch power to the control box cooling fan. The 
thermostat will interrupt power to the cooling fan when the control box 
temperature falls to 100
°F ± 3° (37.8°C ± 1.7°). 
MAIN FAN CIRCUIT 
Power is permanently supplied, through a 10 amp fuse, and through a normally 
closed control box hi-limit thermostat, to the normally open main power switch. 
Power is also supplied to the normally open cooling fan thermostat. Closing the 
main power switch supplies 120VAC to the main fan motor, the cooling fan 
motor, the primary of the control transformer, the conveyor motor and to the 
ignition control. 
BURNER CIRCUIT 
Closing the main power switch supplies 120VAC to the burner blower motor. 
120VAC is also supplied, through the normally closed oven cavity hi-limit 
thermostat, the main fan centrifugal switch (this switch closes when the main 
fan reaches approx. 1600 RPM), to the primary of the burner transformer. 
IGNITION CONTROL 
The ignition control operates on both 24VAC and 120VAC. When the control is 
energized by 24VAC from the transformer, 120VAC is switched by the ignition 
control to the hot surface igniter for 45 seconds for the hot surface igniter warm 
up. The igniter glows red, 24VAC is switched to the gas valve, which opens, 
and ignition should now occur. 
TEMPERATURE CONTROL 
Closing the main power switch supplies 120VAC to the primary of the oven 
control transformer. Secondary voltage, 24VAC, is supplied to the oven control. 
The oven control is set to desired temperature. The thermocouple will provide 
varying millivolts to the oven control. The oven control supplies 120VAC to the 
temperature regulation valve at intermittent intervals to maintain the desired 
temperature. The display on the oven control will indicate when the temperature 
regulation valve is energized. 
NOTE: The display also indicates oven temperature 
CONVEYOR DRIVE 
Closing the main power switch supplies 120VAC to the conveyor motor and to 
the primary of the control transformer. Secondary voltage, 24VAC, is supplied to 
the oven control. Setting the oven control to the desired time outputs voltage, 
through a reversing switch, to the conveyor motor. 
NOTE: The conveyor system uses a hall effect sensor and magnet to prove 
operation of the conveyor motor. If the conveyor motor is not running, “BELT 
JAM” is indicated on the display.