Regency U39-NG1 ユーザーズマニュアル

ページ / 44
Regency
®
 U39 ULTIMATE Direct Vent Freestanding Gas Stove
7
INSTALLATION
8)  Any safety glass removed for servicing 
must be replaced prior to operating the 
appliance.  
9)  To prevent injury, do not allow anyone who 
is  unfamiliar with the operation to use the 
fi replace.  
INSTALLATION 
CHECKLIST
1)  Loate your appliance. Refer to the following 
sections: 
 
a. Locating Your Ultimate Gas Stove
 
b. Exterior Vent Termination Locations
 
c. Clearance to Combustibles
 d. 
Combustion 
and 
Ventilation 
Air
2)  Install Louvers.  Refer to the "Louver 
Installation" section.
3)  Choose a venting option and install 
accordingly.  Refer to the following sections 
where applicable: 
 
a. DV Stove Horizontal Vent Kit
 
     Installation
 b. 
Dura-Vent 
Termination 
Kit
 
c. Set Vent Restrictors. Refer to "Rigid     
    Pipe Venting Arrangement" section.  
 
d. Converting a Class-A Metal Chimney  
    or Masonry Chimney to a Direct Vent  
    system.
4)  Make gas connections. Refer to "Gas 
Connection" section. 
 
Test the pilot. Must be as per diagram. Refer 
to "Pilot Adjustment" section.
5)  If necessary, see the "Conversion from NG 
to LPG" section and "Conversion to Lower 
BTU Rating" section.
6)  Test Gas Pressure. Refer to "Gas Pipe 
Pressure Testing" section .
7)  Install standard and optional features. 
 
Refer to the following sections where 
applicable: 
 
a. Log Set
 b. 
Front 
Door
 c. 
Wall 
Thermostat
 d. 
Remote 
Control
8)  Final check.  Refer to the "Final Check" 
section.
4)  This appliance is Listed for bedroom 
 
installations when used with a Listed Millivolt 
Thermostat. Some areas may have further 
requirements, check local codes before 
installation.
5)  This appliance is Listed for Alcove 
installations, maintain minimum Alcove 
clearances as follows,   minimum width of 
48" (1219mm), a maximum depth of 36" 
(914mm), and minimum ceiling height of 
64"(1626mm).
6)  We recommend that you plan your installation 
on paper using exact measurements for 
clearances and floor protection before 
actually installing this appliance.  Have a 
qualifi ed building inspector review your plans 
before installation.
GENERAL SAFETY 
INFORMATION
1) The 
appliance 
installation 
must 
conform 
with 
local Canadian Electrical Code.
2)  The appliance when installed, must be 
electrically grounded in accordance with 
local codes, or in the absence of local codes 
with the current National Electrical Code, 
ANSI/NFPA 70 or CSA C22.1 Canadian 
Electrical Code.
3)  The  appliance should be inspected for 
shipping damage before use and serviced 
annually by a professional service 
person
. More frequent cleaning may be 
required due to excessive lint from carpeting, 
bedding material, etc. It is imperative that 
control compartments, and circulating air 
passageways of the appliance be kept 
clean and free from excessive lint from 
carpeting.
4)  See general construction and assembly 
instructions. The appliance and vent should 
be enclosed when installed in or passing 
through a living area, where children may 
come in contact with it.  
5)  This appliance must be connected to the 
specifi ed vent and termination cap to the 
outside of the building envelope. Never 
vent to another room or inside a building.  
Make sure that the vent is fi tted as per 
the instructions starting in "Locating Your 
Ultimate Gas Stove" section.
6)  Inspect the venting system annually for 
blockage and any signs of deterioration.   
7)  Venting terminals shall not be recessed into 
a wall or siding.
Before leaving this unit with the customer, 
the installer must ensure that the appliance is 
fi ring correctly and operation fully explained 
to customer
.
This includes:
1)
  Clocking the appliance to ensure the correct 
fi ring rate (rate noted on label) after burning 
appliance for 15 minutes.
2)  If required, adjusting the primary air to ensure 
that the fl ame does not carbon. First allow 
the unit to burn for 15-20 min. to stabilize.
CAUTION: Any alteration to the product that 
causes sooting or carboning that results 
in damage is not the responsibility of the 
manufacturer.
CLEARANCES TO 
COMBUSTIBLES
The clearances listed are MINIMUM distances. 
Measure the clearance to both the appliance 
and the chimney connector. The farthest 
distance is correct if the two clearances do 
not coincide.
 
For example, if the appliance is set as indicated 
in one of the fi gures but the connector is too 
close, move the stove until the correct clearance 
to the connector is obtained.  
This appliance may be installed only with the 
clearances as shown in the situations pictured. 
Do not combine clearances from one type of 
installation with another in order to achieve 
closer clearances.
This unit can be installed on a solid combustible 
surface like a wood fl oor. This unit can also be 
installed directly on carpeting  or vinyl when the 
bottom pedestal cover plate (provided with unit) 
is installed.
Use the minimum clearances shown in the 
diagrams below:
U39-NG1 & U39-LP1 Clearances
A  Side Wall to Unit 
7-1/2" / 190 mm
B  Back Wall to Unit 
6" / 150 mm
E  Side Wall to Unit 
2" / 50 mm
U39-NG1 & U39-LP1 Reference 
Dimensions
C Back Wall to Flue Centerline 11"/280 mm
D  Side Wall to Flue Centerline 20-1/2"/521 mm
F  Side Wall to Flue Centerline  11"/280 mm
Minimum ceiling height is 36" / 914 mm from top 
of unit.
Emissions from burning  wood or gas could 
contain chemicals known to the State of Cali-
fornia to  cause cancer, birth defects or other 
reproductive harm.