CHECKING AND ADJUSTING THE INPUT
1.  Follow steps 1 thru 6 of the OPERATING INSTRUCTIONS.
2.  Attach a pressure gauge or a manometer to the manifold 
pressure tapping and refer to table 10 for correct manifold 
pressure.
3.  Follow steps 7 thru 11 of the OPERATING INSTRUCTIONS.
4.  Use this formula to “clock” the meter.  Be sure that other gas 
consuming appliances are not ON during this interval.
 
3600   x  H  =  Btuh
 
   T
 
Btuh  =  The approximate actual input rate.
 
T  = 
Time in seconds to burn one cubic foot of gas.
 
H  = 
Heating value of the fuel gas in Btu per cubic foot of gas.
EXAMPLE:
 
T  =  9.0 seconds/ft
3
 
H  =  1050 Btu/ft
3
(natural gas)
 
Btuh  =  ?
 
Gas flow through meter:
 
3600    x  1050  =  420,000 Btuh
 
 9.0
Small changes in the input rate may be made by adjusting the 
manifold pressure, see GAS PRESSURE REGULATORS. Under 
no circumstances should you exceed the maximum input rate 
for the boiler given in table 2 on page 6.
5.  Repeat steps 1 thru 6 of the OPERATING INSTRUCTIONS.
6.  Remove the pressure gauge or manometer from the manifold 
pressure tapping. Replace the screw-in plug in the manifold 
pressure tap.
7.  Repeat steps 7 thru 11 of the OPERATING INSTRUCTIONS.  
The boiler will resume normal operation.
 
When the boiler is operating at full capacity, or full gas input, 
it should consume 1 cu. ft. of gas in approximately the time 
indicated in table 10.
TABLE 10.
CONSUMPTION RATE
(Refer to Operating at Full Input or Full Capacity)
Type Gas
Heating 
Value 
Btu/Ft.
Time to Consume 1 cu. ft. of gas (seconds)
HW-
300
HW-
399
HW-
420
HW-
520
HW-
610
HW-
670
Natural
1050
12.6
9.5
9.0
7.3
6.2
5.7
Propane
2500
30.0
22.6
21.4
17.3
14.8
13.4
IMPORTANT
UNDER  NO  CIRCUMSTANCES  SHOULD  THE  GAS  INPUT 
EXCEED THE INPUT SHOWN ON THE BOILER MODEL AND 
RATING PLATE. OVERFIRING COULD RESULT IN DAMAGE 
OR  SOOTING  OF  THE  BOILER.    Minor  variances  from  input 
on rating plate can be corrected by adjustment of gas pressure 
regulators described in GAS PRESSURE REGULATORS section 
of this manual.
The inlet gas pressure must not exceed or be less than the values 
shown on rating plate.