Common Slot ProLiant
460Watts, Common Slot, non-redundant, 92% Efficiency
NOTE: This power supply is needed to support power capping and power monitoring
HP's ProLiant Common Slot Power 460W supply meets multiple Energy Efficiency Initiatives. Climate
Savers Computing Initiative GOLD, ECOS Consulting 80PLUS GOLD and plans on offering models that
meet the Energy Star for Server requirements when they are published.
UPS and PDU Power
Cord Matrix
Please see the UPS and PDU cable matrix's on the HP Power Protection and Management page. Under
Power Cords, click on the "HP Power Cord Matrix" link. That link will list cable descriptions, requirements,
and specifications for UPS and PDU units. Please see the following link:
System Fans
5 dual rotor fans ship standard
Ultra Thin Rack
Deployment Overview
For the Ultra Thin Rack Deployment Overview, including best practices for the HP ProLiant DL320 G6,
please see the following URL: 
.
Required Cabling
For required cabling information, refer to the Web site at: 
Operating Systems and
Virtualization Software
Support for ProLiant
Servers
NOTE: Support differences will exist between the SATA and SAS configurations.
NOTE: For more information on HP's Certified and Supported ProLiant Servers for OS and Virtualization
Software and latest listing of software drivers available for your server, please visit our Support Matrix at:
.
Rack Airflow Requirements
Rack 10000 G2 series Cabinets
The increasing power of new high-performance processor technology requires increased cooling
efficiency for rack-mounted servers. The 10000 G2 Series Racks provide enhanced airflow for maximum
cooling, allowing these racks to be fully loaded with servers using the latest processors.
CAUTION: If a third-party rack is used, observe the following additional requirements to ensure adequate
airflow and to prevent damage to the equipment:
Front and rear doors: If your 42U server rack includes closing front and rear doors, you must allow
5,350 sq cm (830 square inches) of hole evenly distributed from top to bottom to permit adequate
airflow (equivalent to the required 64 percent open area for ventilation).
Side: The clearance between the installed rack component and the side panels of the rack must be
a minimum of 7 cm (2.75 inches)
CAUTION: Always use blanking panels to fill all remaining empty front panel U-spaces in the rack. This
arrangement ensures proper airflow. Using a rack without blanking panels results in improper cooling that
can lead to thermal damage.
NOTE: For additional information, refer to the Setup and Installation Guide or the Documentation CD
provided with the server, or to the server documentation located in the Support section at the following