Electrolux EAS(C,E)12C2ASK(W,S,M) ユーザーズマニュアル

ページ / 28
4. Flaring work
A) Firmly hold copper pipe in a die in 
the dimension shown in the table 
below.
1,3
1,6
1,8
2,4
Máx.
0,7
1,0
1,0
2,2
A (mm)
Mín.
OUTER
DIAMETER (mm)
6,35
9,53
12,70
16
Connection Adjustment
1.  Align the pipes to be connected.
2.  Unscrew the flare nut with your 
fingers and then with a wrench and 
screw wrench, as shown in the 
following figure.
OUTER
DIAMETER (mm)
6,35
9,53
12,70
16
TIGHTENING
TORQUE(cm)
1570 (160 kgf/cm)
2940 (300 kgf/cm)
4900 (500 kgf/cm)
7360 (750 kgf/cm)
ADDITIONAL TIGHTENING
TORQUE(cm)
1960 (200 kgf/cm)
3430 (350 kgf/cm)
5390 (550 kgf/cm)
7850 (800 kgf/cm)
Caution: Excessive torque can 
break nut depending on installation 
conditions.
19 electrolux refrigerant pipe connection
Electrical work
1. If there is serious safety problem 
about the power supply, the 
technicians should refuse to install 
the air conditioner and explain to 
the client until the problem is 
solved.
2. Power voltage should be in the 
range of 90%~110%of rated 
voltage.
3. The creepage protector and main 
power switch with a 1.5 times 
capacity of Max. Current of the unit 
should be installed in power circuit.
4. Ensure the air conditioner is 
grounded well.
5. According to the attached Electrical 
Connection Diagram located on the 
panel of the outdoor unit to connect 
the wire.
6. All wiring must comply with local 
and national electrical codes and be 
installed by qualified and skilled 
electricians.
7. An individual branch circuit and 
single receptacle used only for this 
air conditioner must be available. 
See the following table for 
suggested wire sizes and fuse 
specifications:
Electric safety regulations for the initial Installation
electrical work
 electrolux 20
Bar
Copper
pipe
Handle
Clamp
handle
Yoke
Red arrow mark
Flare
nut
Pipings
Indoor unit
tubing
MODEL
INPUT RATED AMP
Switch / Fuse
POWER SUPPLY
CABLE
SIZE
Note: 
The supply voltage must be consistent with the rate voltage of the air conditioner.
 
9000 Btu’s 
 
  
 
12000 Btu’s
18000 Btu’s
24000 Btu’s
220-240V~/ 50Hz 
220-230V~/ 60Hz 
220-240V~/ 50Hz 
220-230V~/ 60Hz
220-240V~/ 50Hz 
220-230V~/ 60Hz 
10A
16A
25A
32A
1 mm²
1,5 mm²
2,5 mm²
> 2,5 mm²