1.  Never fail to have an individual power circuit specifically for the air 
conditioner. As for the method of wiring, be guided by the circuit diagram 
posted on the inside of control cover.
2.  The screw which fasten the wiring in the casing of electrical fittings are 
liable to come loose from vibrations to which the unit is subjected during 
the course of transportation. Check them and make sure that they are all 
tightly fastened. (If they are loose, it could cause burn-out of the wires.)
3.  Specification of power source.
4.  Confirm that electrical capacity is sufficient.
5.  See to that the starting voltage is maintained at more than 90 percent of the 
rated voltage marked on the name plate.
6.  Confirm that the cable thickness is as specified in the power source 
specification.
7.  Always install an earth leakage circuit breaker in a wet or moist area.
8.  The following would be caused by voltage drop. Vibration of a magnetic 
switch, which will damage the contact point, fuse breaking, disturbance of 
the normal function of the overload.
9.  The means for disconnection from a power supply shall be incorporated in 
the fixed wiring and have an air gap contact separation of at least 3mm in 
each active (phase) conductors.
Caution
After the confirmation of the above conditions, prepare the wiring as follows:
Air purging
Air and moisture in the refrigerant system have undesirable effects as 
indicated below:
1.  Pressure in the system rises.
2.  Operating current rises.
3.  Cooling or heating efficiency 
drops.
4.  Moisture in the refrigerant circuit 
may freeze and block capillary 
tubing.
5.  Water may lead to corrosion of 
parts in the refrigeration system.
6.  Therefore, the indoor unit and 
tubing between the indoor and 
outdoor unit must be leak tested 
and evacuated to remove any 
noncondensables and moisture 
from the system.
25 electrolux electrical work
Air purging with vacuum pump
1.  Check that each tube(both liquid and gas side tubes) between the indoor 
and outdoor units have been properly connected and all wiring for the test 
run has been completed. Remove the service valve caps from both the gas 
and the liquid side on the outdoor unit. Note that both the liquid and the gas 
side service valves on the outdoor unit are kept closed at this stage.
2.  When relocate the unit to another place, perform evacuation using vacuum 
pump.
3.  Pipe length and refrigerant amount:
Caution in handling the packed valve
1.   Open the valve stem until it hits against the stopper. Do not try to open it 
further.
2.   Securely tighten the valve stem cap with a spanner or the like. Valve stem 
cap tightening torque (See Tightening torque table in page 19).
electrical work
 electrolux 26
Air purging
metod
Less than 5 m
5~10 m
Additional amount of
refrigerant to be charged
Connective
pipe length
Use vacuum pump.
Use vacuum pump.
Half union
Refrigerant
A
C
D
B
Packed valve
Gas
Indoor unit
Outdoor unit
Flare nut
Stopper
Cap
Valve stem
Valve body
Liquid side: Ö6.35
(Pipe lenght) x 30g