Section 2 — Post Installation Start-up and Adjustments
Guardian Air-cooled 7 kW, 12 kW and 15 kW Generators
If this procedure or equipment are not available,
locate the nearest Generac Guardian Dealer and they
can perform the adjustments.
NOTE:
A service fee may be charged for this adjustment.
2.7
ENGINE GOVERNOR ADJUSTMENT
If both AC frequency and voltage are correspondingly
high or low, adjust the engine governor as follows:
2.7.1
7 KW UNITS
1. Loosen the governor clamp bolt (Figures 2.3 and
2.4).
2. Hold the governor lever at its wide open throttle
position, and rotate the governor shaft clockwise
as far as it will go. Then, tighten the governor
lever clamp bolt to 70 inch-pounds (8 N-m).
3. Start the generator; let it stabilize and warm up
at no-load.
4. Connect a frequency meter across the generators
AC output leads.
5. Turn the speed adjust nut to obtain a frequency
reading of 63 Hz.
6. When frequency is correct at no load, check the
AC voltage reading. If voltage is incorrect, the volt-
age regulator may require adjustment.
Figure 2.3 — Single Cylinder Engine Governor
Adjustment
2.7.2
12 KW AND 15 KW UNITS
1. Loosen governor clamp bolt (See Figure 2.4).
Figure 2.4 — V-twin Engine Governor
Adjustment
2. Completely remove the idle spring.
3. With governor arm at wide open throttle position,
rotate governor shaft fully clockwise. Tighten
clamp bolt to 84 inch-pounds.
4. Start unit and apply full load. Use full load speed
adjust screw (Figure 2.5) to adjust frequency to
58 Hz.
5. Remove load, stop engine, loosen the idle adjust
screw and reconnect the idle spring.
6. Using a hand, push the governor arm to the
closed throttle position. Make sure the idle spring
does not stretch at all.
7. Restart the unit.
8. Slowly turn the idle adjust screw to adjust the no-
load idle frequency to 63-63.5 Hz.
9. The governor is now set.
Figure 2.5 — V-twin Full Load Speed Adjust
Screw
Full Load Speed Adjust Screw
Governor Clamp Bolt
Governor
Shaft
(Rotate
Clockwise)
Idle Spring
No Load Idle
Adjustment Screw
GOVERNOR
SHAFT
ADJUST
SCREW
GOVERNOR
CLAMP
BOLT
Generac® Power Systems, Inc.
13