Installation Procedures
ELECTRICAL REQUIREMENT
Electric wire size and fuse capacity:
Table 5
ELECTRICAL WIRING
1. INDOOR UNIT SIDE
(1) Remove the electric component box.
(2) Pull out the electric component box.
Fig.28
(3) Remove the electric component box cover.
Fig. 29
Base
Electric component box cover
Remove the three tapping screws.
(1) Remove the cord clamp.
(2) Process the end of the connection cords to the
     dimensions shown in Fig.34.
(3) Connect the end of the connection cord fully into the
      terminal block.
(4) Wiring
(4) Fasten the connection cord with a cord clamp.
(5) Fasten the end of the connection cord with the
     screw.
Electric component box
CAUTION
Be careful not to pinch the lead wires
between the electric component box
and base.
CAUTION
(1) Match the terminal block numbers and connection
    cord colors with those of the outdoor unit.
    Erroneous wiring may cause burning of the electric
    parts.
(2) Connect the connection cords firmly to the terminal
    block. Imperfect installation may cause a fire.
(3) Always fasten the outside covering of the connection
    cord with the cord clamp.(If the insulator is chafed,
    electric leakage may occur.)
(4) Always connect the ground wire.
17
Power supply
cord (mm
2
)
Fuse capacity(A)
2.5
30
Connection cord
         (mm
2
)
Type
AC182ACERA
0.75
AC142ACERA
AC242ACERA
Fig. 26
Electric component box
Fig. 27
Electric component box
Remove the four tapping
screws.
CAUTION
Do not remove the screws. If the screws
are removed, the electric component
box will fall.
060309*****
1 2
3 N L
1 2
3
L N
Power supply: 1PH, 220-230V~, 50Hz
OUTDOOR UNIT
TERMINAL BLOCK
INDOOR UNIT
TERMINAL BLOCK
0.75
0.75
2.5
4.0
30
4.0