15
4) Press the 
 up or 
 down button to increase or decrease the - (minus) differential in 
.9°F increments.
Note: The - value can be adjusted between -0.9 and -6.3°F in .9°F increments (-0.5 to 
-3.5°C in .5°C increments).
5) Press the 
 service button to save the - (minus) setting. The - (minus) sign will turn off 
and the display will change to the + (plus) differential setting.
6) Press the MANUAL DEFROST button to return to the menu screen. Press and hold 
both the
 
 button and the 
 service button for 5 seconds to exit the setting mode 
and return to the temperature display.
c) High Temperature Alarm Delay Time (F3)
This value should only be changed after consulting with the factory. To change the high 
temperature alarm delay time, follow the steps below.
1) Press and hold both the
 
 button and the 
 service button for 5 seconds. "F0" should 
appear in the display window. Press the MANUAL DEFROST button until "F3" appears 
in the display window.
2) Press the 
 service button to display the current setting (default: 2). Press the 
 up 
or 
 down button to increase or decrease the high temperature alarm delay time. 
Note: The time can be adjusted between 0 and 180 minutes in 60 minute increments. 
The display corresponds to time as follows:
Display Detection Time 
(minutes)
0
0
1
60
2
120
3
180
3) Press the 
 service button to save the setting.
4) Press the MANUAL DEFROST button to return to the menu screen. Press and hold 
both the
 
 button and the 
 service button for 5 seconds to exit the setting mode 
and return to the temperature display.
d) Low Temperature Alarm Delay Time (F4)
This value should only be changed after consulting with the factory. To change the low 
temperature alarm delay time, follow the steps below.
1) Press and hold both the
 
 button and the 
 service button for 5 seconds. "F0" should 
appear in the display window. Press the MANUAL DEFROST button until "F4" appears 
in the display window.
2) Press the 
 service button to display the current setting (default: 1). Press the 
 up 
or 