2) To change the setpoint, press and hold the 
 button while pressing the  
 up or 
 
down button. 
Allowable Setpoint Range
Default
Fahrenheit
Celsius
Fahrenheit
Celsius
Refrigerator +21 to +54°F -6 to +12°C
37°F
3°C
Freezer
-13 to +19°F
-25 to -7°C
0°F
-18°C
3) The new setpoint will be saved automatically 10 seconds after releasing the buttons.
Note: For refrigerators and freezers, the temperature differential for the compressor to 
turn off is -3.6°F (-2.0°C).
2. Settings and Diagnostics Menu
Press and hold both the 
 button and the  
 service button for 5 seconds to enter the 
settings and diagnostics menu. Press the MANUAL DEFROST button to scroll through 
the menu and the  
 service button at any point to view the current setting. Press the 
MANUAL DEFROST button to return to the menu screen. Press and hold both the
 
 
button and the 
 service button for 5 seconds to exit the setting mode and return to the 
temperature display.
Note: If there is no input for 60 seconds, the display will revert to the temperature display.
Code Item
Setting and Display Range
Default
Refrigerator
Freezer
F0 Defrost Interval
1 to 12 hours in 1 hour increments
6
6
F2 Setpoint Temperature Differential 
(upper and lower)
0 to 6.3°F in increments of .9°F – upper
(0 to 3.5°C in increments of .5°C) 
-0.9 to -6.3°F in increments of .9°F – lower 
(-0.5 to -3.5°C in increments of .5°C) 
3.6, -3.6 °F
(2.0, -2.0 °C)
(decimal 
is not 
displayed)
3.6, -3.6 °F
(2.0, -2.0 °C)
(decimal 
is not 
displayed)
F3 High Temperature Alarm Delay 
Time (cabinet temperature)
0 to 180 minutes in 60 minute increments 
(0=0; 1=60; 2=120; 3=180 minutes)
2
2
F4 Low Temperature Alarm Delay 
Time (cabinet temperature)
0 or 60 minutes 
(0=0; 1=60 minutes)
1
1
F5 Temperature Display
Fahrenheit or Celsius
°F
°F
F6 Alarm History
Displays alarm history - maximum 8 
alarms
NA
NA
F7 Compressor Run Time
Displays run time between two most 
recent defrosts
NA
NA
F8 Not in Use
-
Flashes "--" 
and "00"
Flashes "--" 
and "00"
FA High Temperature Shutoff 
Temperature Setting (clogged 
filter thermistor)
149 to 167°F
(65 to 75°C)
163°F 
(73°C)
(for °F, only 
the last two 
digits are 
displayed 
and "-" 
flashes)
158°F 
(70°C)
(for °F, only 
the last two 
digits are 
displayed 
and "-" 
flashes)
Fb Not in Use
-
AL
AL