D. Settings and Diagnostics
1. Guarded Access Menu 
At start up the control board revision number is displayed. ("r_##", where "##" indicates 
the current board revision on that model). Three settings can be viewed and changed 
from this menu; temperature setpoint, defrost frequency, and temperature display scale. 
a) Temperature Setpoint 
The temperature setpoint is the value for the average cabinet temperature. The 
temperature differential for the compressor to turn on and off is ±3°F of the setpoint. For 
example, setpoint = 36°F, compressor on at 39°F, compressor off at 33°F. If necessary, 
adjust the setpoint temperature as follows:
1) Press and hold the up/down arrows simultaneously for 3 seconds. The current setpoint 
temperature will be displayed. 
) To change the setpoint, press the up/down arrows until the desired value is displayed. 
For refrigerators the cabinet temperature is adjustable between 36°F and 50°F (.°C 
and 10°C). The factory default is 36°F (.°C). For freezers the cabinet temperature is 
adjustable between -10°F and 5°F (-3.3°C and -3.9°C). The factory default is -3°F 
(-19.4C).
3) To save the value, press "ENTER" repeatedly until you have cycled through the menu 
and the unit returns to the normal display mode. If you do not cycle through the menu 
and no button is pressed in 15 seconds, the display will return to normal and the 
setpoint will remain unchanged.
b) Defrost Frequency  
(1a) Defrost for Refrigerators - Control Board Revision 22 and earlier
This unit uses an off-cycle defrost. When a sensor in the evaporator coil reaches 13°F    
(-10°C) (8°F, -13.3°C for Pass Thru) the unit enters defrost. When the sensor reaches 
40°F (4.4°C) the unit ends defrost. No adjustment is available or needed from the 
control board.
With control board revision  and earlier, the cabinet temperature is displayed, even 
during defrost.
(1b) Defrost for Refrigerators - Control Board Revision 23 and later
This unit uses an off-cycle defrost. When a sensor in the evaporator coil reaches 13°F 
(-10°C) (8°F, -13.3°C for Pass Thru) the unit enters defrost. When the sensor reaches 
40°F (4.4°C) the unit ends defrost. Units with a control board of revision level R3 
and later (board revision level can be seen on display at power up) also feature an 
adjustable time-initiated defrost along with the normal temperature-initiated defrost.
The time-initiated defrost is factory set at 0. Before changing this setting, contact the 
HOSHIZAKI Technical Support Department for recommendations. To change the 
time-initiated defrost, follow the steps in "(3) Defrost Frequency Adjustment" later in this 
section. With control board revision 3 and later the cabinet temperature is not displayed 
during defrost, "dEF" is displayed in its place.