Alcatel-Lucent 6850-48 ハードウェアマニュアル

ページ / 188
OmniSwitch 6850 Series Chassis and Hardware Components
OmniSwitch 6850 Series Power Supplies
OmniSwitch 6850 Series Hardware Users Guide
September 2009
page 2-85
You can also attach the power supplies to the back of an OmniSwitch 6850 Series chassis directly as well 
as using cables at the same time, as shown in the diagram below. 
Redundant 510W-PoE
DC Power Supply Considerations
In addition to the installation steps described in 
and 
DC power supplies (e.g., the PS-
120W-DC) have the following additional considerations:
• Connect to a -48V or -60V reliably grounded DC SELV source.
• Use common DC return connections for the DC power supplies. The DC return terminal conductor 
should be connected to the equipment frame.
• The Branch Circuit Overcurrent Protection must be rated a Maximum of 15A.
• Use 12AWG solid conductors only.
• A readily accessible disconnect device that is suitably approved and rated shall be incorporated in the 
field wiring.
Twisted pair wire (red and black) for a DC power supply
Note. Refer to the wiring diagram for information on connecting the DC power supply to a DC power 
source.
17.6 inches
MIN 1 TURN PER 1.5
HALF TURN PER .75
Black
Red