                                  Run or start capacitor defective                       Replace
                                  Loose connection                                             Check and tighten all connections.
Condenser fan runs,  Compressor stuck, grounded or open               Wait for 2 hours for overload to reset.
compressor doesn't   motor winding, open internal overload            Replace compressor if still open.
                                  Low voltage condition                                     At compressor terminals, voltage must be within 10% of rating
                                                                                                           plate volts when unit is running.
                                  Low voltage condition                                     Add start kit components
                                  Incorrect voltage                                              At compressor terminals, voltage must be within 10% of rating
Compressor                                                                                        plate volts when unit is running.
short-cycling             Defective overload protector                           Replace - check for correct voltage
                                  Refrigerant undercharge                                   Add refrigerant
Register sweat           Low evaporator airflow                                   Increase blower speed or reduce restriction - replace air filter
                                  Restriction in liquid line,                                 Replace defective components
 High head - Low     metering device or filter drier
vapor pressures         Flowrator piston size too small                        Change to correct size piston
                                  Incorrect capillary tubes                                   Change coil assembly
                                  Blocked outdoor coil                                        Clear away leaves and other debris
High head - High      Refrigerant overcharge                                    Correct system charge
 or normal vapor       Condenser fan not running                                Repair or replace
 pressures                  Air, non-condensibles or                                   Recover refrigerant, evacuate &
                                  moisture in system                                            recharge, add filter drier
Low head - High      Flowrator piston size too large                         Change to correct size piston
vapor pressures         Defective compressor valves                           Replace compressor
                                  Incorrect capillary tubes                                  Replace coil assembly
Low vapor - cool      Low evaporator airflow                                   Increase blower speed or reduce restriction - replace air filter
 compressor - iced    Operating below 65  F outdoors                      Add low ambient kit
evaporator coil          Moisture in the system                                    Recover refrigerant, evacuate & recharge, add filter drier
High vapor                Excessive load                                                 Recheck load calculation
pressure                     Defective compressor                                      Replace
Fluctuating head        Air or non-condensibles in system                  Recover refrigerant, evacuate & recharge.
and vapor pressures
Pulsing noise at         Air or non-condensibles in system                  Recover refrigerant, evacuate & recharge
metering device
or liquid line
Symptom                  Possible Cause                                               Remedy
                                  Power off or loose electrical connection         Make sure main switch is ON. Check and tighten all connections.
                                  Incorrect thermostat setting                             Set thermostat correctly
No cooling                Defective contactor                                          Check for 24V at contactor coil.
                                  Open circuit breaker of blown fuses                Reset or replace
                                  Defective transformer                                      Check wiring - Replace it.
                                  Interconnecting low voltage wiring damage    Replace thermostat wiring
                                  Dirty filters                                                      Clean & replace
                                  Indoor air blockage                                          Check supply registers and return grills for blockage.
                                  Blocked outdoor coil                                       Clear away leaves and other debris
                                  Improperly sized unit                                       Recalculate load
Insufficient Cooling  Improper airflow                                              Check - should be 400CFM/Ton
                                  Incorrect refrigerant charge                              Charge correctly per instruction.
                                  Air, non-condensibles or moisture in system   Recover refrigerant, evacuate & recharge, add filter drier
                                  Incorrect voltage                                              At compressor terminals, voltage must be within
                                                                                                           10% of rating plate volts when unit is running.
Water on floor or in
furnace                      Blocked condensate drain and "P" trap           Remove blockage