Spectra 2K Library AIT-4 Drive Upgrade
2
Loading the Firmware Code Tape
To load the firmware tape:
1.
Drives are located at the bottom of the library. Move the picker away from its 
lowest position, so that you can access the drives:
Open and close the library door, which forces the picker to move.
When the picker is positioned in the middle or the top of the library, 
open the door again.
2.
Carefully insert the tape into the drive with the write-protect tab facing out and 
the window facing up. If you have a two-drive library, make sure you load the 
tape into Drive 1—the drive closest to the data cartridge magazine.
Preparing the Library
1.
Power off the library.
2.
Disconnect the SCSI cable from the back of the library.
3.
Move the library to a position that provides easy access to the front and rear of 
the library. 
4.
Locate the configuration switches on the rear of the library, and write down the 
settings of the library configuration switch and the SCSI ID switch.
5.
Use a small screwdriver to turn the library configuration switch to and the 
library SCSI ID switch to 7.
Loading the New Firmware
1.
With the library door open and the picker away from its lowest position, power 
on the library. The library begins the firmware update process, during which time 
the picker parks at the bottom of the library, and its LED turns amber for the 
duration of the firmware upgrade. This process typically requires less than five 
minutes.
2.
When the drive ejects the tape, the upgrade is complete; remove the tape from 
the drive.
If the tape doesn’t automatically eject from the drive: make sure the 
picker is parked at the bottom of the library, then press Eject on the front 
of the drive.