Eaton CBL105 ユーザーズマニュアル
© 2008 Eaton Corporation. All Rights Reserved. All specifications are subject to change without notice.
www.pulizzi.com • pulizzisales@eaton.com • 800-870-2248 • Fax: 605-334-4999
2
REQUIRED CABLE ASSEMBLY OPTIONS:
CBL103: 120V/30A with 10/3 cable 9’ long terminated with a NEMA L5-30P
CBL104: 240V/30A with 10/3 cable 9’ long terminated with a NEMA L6-30P
CBL105: 240V/30A with 3x4.0mm Harmonized cable 9’ long terminated with an IEC 60309 32A plug
CBL104: 240V/30A with 10/3 cable 9’ long terminated with a NEMA L6-30P
CBL105: 240V/30A with 3x4.0mm Harmonized cable 9’ long terminated with an IEC 60309 32A plug
This system is designed to be controlled Locally or Remotely via a remote control panel. SOLD SEPARATELY
SPECIFICATIONS
PC5585-AB
PC5585-AB1/MTD
PC5585-AB/MTD
PC5585-CF
PC5585-CF1/MTD
PC5585-CF/MTD
Approvals
UL/cUL, TUV, CE
UL/cUL, TUV, CE
UL/cUL, TUV, CE
UL/cUL, TUV, CE
UL/cUL, TUV, CE
UL/cUL, TUV, CE
Voltage I/O, (50/60Hz)
120V/240V~
120V/240V~
120V/240V~
120V/240V~
120V/240V~
120V/240V~
Current Input
20A
20A
20A
30A
30A
30A
Current Output
16A
16A
16A
24A
24A
24A
Full Load VA
1920VA/3840VA
1920VA/3840VA
1920VA/3840VA
2880VA/5760VA
2880VA/5760VA
2880VA/5760VA
Circuit Breaker
20/20A
20/20A
20/20A
20/20/30A
20/20/30A
20/20/30A
Multiple Time Delay
Remote only
MTD™ Up
MTD™ Up/Down
Remote only
MTD™ Up
MTD™ Up/Down
Outlets: IEC 60320
Type C13
Type C13
Type C13
Type C13
Type C13
Type C13
EMI/RFI Filter
20A
20A
20A
30A
30A
30A
Surge Suppression
270V
270V
270V
270V
270V
270V
RACK MOUNTED
•
19” x 2U (3.4”) x 8.5” (recessed)
•
Approximate shipping weight: 18 lbs.
IEC 60320 OUTLETS (14)
•
12 switched (4 per switched section) on
the front panel and 2 unswitched on the
rear panel. Each outlet is rated by UL
and CSA at 125V~ / 15A or by VDE at
250V~ / 10A
the front panel and 2 unswitched on the
rear panel. Each outlet is rated by UL
and CSA at 125V~ / 15A or by VDE at
250V~ / 10A
REMOTE SELECTION SWITCH
•
Local: Power “on” to the switched outlets
•
Off: When breaker is “on” but this switch
is in the “off” mode, you will have power
to the unswitched outlets only
is in the “off” mode, you will have power
to the unswitched outlets only
•
Remote: Power “on/off” to the switched
outlets via a remote device
outlets via a remote device
•
Latching remote: PC5585-CF1/LT
only - the selection switch is wired for
Remote/Off/Remote - There is no local
control
only - the selection switch is wired for
Remote/Off/Remote - There is no local
control
VOLTAGE SELECTION SWITCH
•
120V~ Single Phase 50/60Hz
•
240V~ Single Phase 50/60Hz
EMI/RFI FILTERING
•
Common Mode Line to Ground
•
Differential Mode Line to Line
SPIKE/SURGE SUPPRESSION
•
Line to Line
(3 N/O) REMOTE I/O PORTS
•
Remote on/off and EPO control, EPO
overrides remote and local control
overrides remote and local control
•
Sequence Power Up additional
equipment down line (standard on all units)
equipment down line (standard on all units)
•
Latching remote - (N/C) EPO,
momentary start on PC5585-CF1/LT only
momentary start on PC5585-CF1/LT only
POWER INPUT
•
External terminal block for power input is
on the rear panel
on the rear panel
•
High Voltage Cover with attached
cable/plug is available, reference below
part numbers
part numbers
MULTIPLE TIME DELAY (MTD™) (Optional)
•
After Section 1 powers up, 4-seconds
later Section 2 powers up, which is
later Section 2 powers up, which is
followed 4-seconds later by Section 3.
Four seconds later the sequenced remote
activates the next system in line
Four seconds later the sequenced remote
activates the next system in line
•
Models with (/MTD) sequence power up
and power down in reverse order
and power down in reverse order
•
Models with (1/MTD) sequence power
up but not down
up but not down
•
Models without MTD will power up all 12
switched outlets at once
switched outlets at once
•
Sequenced remote is standard on all
systems
systems
(6) INDICATOR LIGHTS
•
(1) Main power “on”
•
(1) Each, Section 1, 2, 3 power “on”
•
120V~ or 240V~ indicator to show which
voltage is selected
voltage is selected
OVERLOAD CIRCUIT PROTECTION
•
Electromagnetic breaker provides manual
on/off switching and trips in an overload
condition
on/off switching and trips in an overload
condition
Front
Back