Microwave Hood Combination
PRODUCT MODEL NUMBERS
KMHC319E
KMHP519E
KMHS120E
Rectangular to Round Transition: 
NOTE: The minimum 3" (7.6 cm) clearance must exist between the top 
of the microwave oven and the rectangular to round transition piece so 
that the damper can open freely and fully.
Because Whirlpool Corporation includes a continues commitment to improve our 
products, we reserve the right to change materials and specifications without notice.
Dimensions are for planning purposes only. For complete details, see Installation 
Instructions packed with product. Specifications subject to change without notice.
VENTING REQUIREMENTS
Required:
•  A 120 volt, 60 Hz, AC only, 15- or 20-amp electrical supply with a fuse 
or circuit breaker.
Recommended:
•  A time-delay fuse or time-delay circuit breaker.
•  A separate circuit serving only this microwave oven.
ELECTRICAL REQUIREMENTS
Ref. W10724870A
2/10/15
Page 1 of 2
A.  Roof cap
B.  6" (15.2 cm) min. diameter round vent
C.  Elbow (for wall venting only)
D.  Wall cap
E.   3
1
4
" x 10" to 6" (8.3 x 25.4 cm to 15.2 cm) 
rectangular to round transition piece
F.  Vent extension piece, at least 3" (7.6 cm) high
A
B
C
E
F
D
3" (7.6 cm)
Recommended Standard Fittings
The following length equivalents are for use when figuring vent length. 
See the examples in “Recommended Vent Length.”
A.  Rectangular to round transition piece: 3
1
4
" x 10" to 6" = 5 ft 
(8.3 x 25.4 cm to 15.2 cm = 1.5 m)
B.  Roof cap: 3
1
4
" x 10" = 24 ft (8.3 x 25.4 cm = 7.3 m)
C.  90° elbow: 3 " x 10" = 25 ft (8.3 x 25.4 cm = 7.6 m)
D.  90° elbow: 6" = 10 ft (15.2 cm = 3 m)
E.   Wall cap: 3
1
4
" x 10" = 40 ft (8.3 x 25.4 cm = 12.2 m)
F.   45° elbow: 6" = 5 ft (15.2 cm = 1.5 m)
G.  90° flat elbow: 3
1
4
" x 10" = 10 ft (8.3 x 25.4 cm = 3 m)
A                           B                            C
D                  E                    F               G
Recommended Vent Length 
A 3
1
4
" x 10" (8.3 x 25.4 cm) rectangular or 6" (15.2 cm) round vent 
should be used.
The total length of the vent system including straight vent, elbow(s), 
transitions and wall or roof caps must not exceed the equivalent of 
140 ft (42.7 m) for either type of vent. See “Recommended Standard 
Fittings” section for equivalent lengths.
For best performance, use no more than three 90° elbows.
To calculate the length of the system you need, add the equivalent 
lengths of each vent piece used in the system. See the following 
examples:
3
1
4
" x 10" (8.3 x 25.4 cm) vent system = 73 ft (22.2 m) total 
A                                          B
C
6 ft (1.8 m)
2 ft
(0.6 m)
A.   One  3
1
4
" x 10" (8.3 x 25.4 cm) 90° elbow = 25 ft (7.6 m)
B.  1 wall cap = 40 ft (12.2 m)
C.  2 ft (0.6 m) + 6 ft (1.8 m) straight = 8 ft (2.4 m)
6" (15.2 cm) vent system = 73 ft (22.2 m) total 
A                                                                  B
C                                  D
6 ft (1.8 m)
2 ft
(0.6 m)
A.  Two 90° elbows = 20 ft (6.1 m)
B.  1 wall cap = 40 ft (12.2 m)
C.  1 rectangular to round transition piece = 5 ft (1.5 m)
D.  2 ft (0.6 m) + 6 ft (1.8 m) straight = 8 ft (2.4 m)
If the existing vent is round, a rectangular to round transition piece must 
be used. In addition, a rectangular 3" (7.6 cm) extension vent between 
the damper assembly and rectangular to round transition piece must be 
installed to keep the damper from sticking.