Honeywell Bypass Drum Humidifier (HE120A) インストール手順

ページ / 48
HE120 BY-PASS DRUM HUMIDIFIER
69-1860EF—01
4
BEFORE YOU BEGIN
When Installing this Product…
1.
Read these instructions carefully. Failure to follow them 
could damage the product or cause a hazardous condi-
tion.
2.
Installation of this Humidifier requires several steps. 
Read and understand instructions completely before 
beginning installation.
3.
After installation is complete, check out product opera-
tion as provided in these instructions.
STEP 1: DETERMINE BEST LOCATION
CAUTION
Freezing Water Hazard. 
Can result in water damage to property. 
Locate Humidifier where the ambient temperature is 
between 32
o
F and 160
o
F.
1.
Select a location to mount the Humidifier on the supply 
(warm air) or return duct. See Fig 1.
Select a location that can not damage the air 
conditioner coil during installation.
Do not locate Humidifier on furnace cabinet.
Allow adequate clearance in front of and above the 
Humidifier so you can easily remove cover and 
perform maintenance.
Allow enough space for the drain or overflow tube.
Mount Humidifier in conditioned (heated) space to 
prevent freezing.
Select a location where the 3 ft. of Bypass Duct is 
adequate to connect the Humidifier to the Bypass 
Collar.
Fig. 1. Typical Humidifier installation locations.
NOTE:
The Bypass Duct can be connected to either side of 
the Humidifier Housing. See Fig. 2.
2.
Select a location for the Bypass Collar on the opposite 
duct. See Fig. 1. (The Humidifier is designed to allow 
Bypass Duct mounting on either side of the Humidifier. 
See Fig. 2.) 
Do not locate Bypass Collar on furnace cabinet.
Select a location where the 3 ft. of Bypass Duct is 
adequate to connect the Humidifier to the Bypass 
Collar.
Allow enough room for the optional Damper.
Fig. 2. Available Bypass configurations.
M12248D
HORIZONT
AL
DOWN
FLO
LOWBOY
HIGHBOY
HUMIDIFIER
BYPASS 
COLLAR