  NEBS GR-1089 Installation and Caution Instructions
NEBS GR-1089 Installation and Caution Instructions
The following are NEBS GR-1089 installation and caution instructions.
Caution
The intra-building ports (Ethernet and serial) of the equipment or subassembly is suitable for connection 
to intra-building or unexposed wiring or cabling only. The intra-building ports of the equipment or 
subassembly must not be metallically connected to interfaces that connect to the outside plant (OSP) or 
its wiring. These interfaces are designed for use as intra-building interfaces only (Type 2 or Type 4 ports 
as described in GR-1089-CORE) and require isolation from the exposed OSP cabling. The addition of 
primary protectors is not sufficient protection in order to connect these interfaces metallically to OSP 
wiring. 
The Cisco Unified Computing System (UCS) has AC power ports that are intended for deployments 
where an external Surge Protective Device (SPD) is utilized at the AC power service equipment (see 
definition in National Electric Code). 
The Cisco UCS is designed for a Common Bonding Network (CBN) installation. 
The Cisco UCS can be installed in network telecommunication facilities or locations where the 
National Electric Code applies. 
An electrical conducting path shall exist between the product chassis and the metal surface of the 
enclosure or rack in which it is mounted or to a grounding conductor. Electrical continuity shall be 
provided by using thread-forming type mounting screws that remove any paint or nonconductive 
coatings and establish a metal-to-metal contact. Any paint or other nonconductive coatings shall be 
removed on the surfaces between the mounting hardware and the enclosure or rack. The surfaces 
shall be cleaned and an antioxidant applied before installation. 
The DC return connection to this system should remain isolated from the system frame and chassis 
(DC-I) . 
The nominal DC operating voltage is -48 VDC. 
The intra-building RJ-45 Ethernet ports of the equipment or subassembly must use shielded 
intra-building cabling or wiring that is grounded at both ends.  
UL Symbols
This caution symbol might appear on the UL label on your server. The meaning of this 
symbol is as follows:
Caution: Slide/rail mounted equipment is not to be used as a shelf or a work space.