Cooling Sub-System
Intel® Server System SR1695GPRX TPS
Revision
1.5
Intel order number: G11332-006
32
Figure 17. Air Duct Position in System
4.5
Drive Bay Population Requirement
In order to maintain system thermal requirements, you must fully populate all hard drive bays.
Hard drive trays used for hot-swap drives must either have a hard drive installed or not have a
hard drive installed.
Hard drive trays used for hot-swap drives must either have a hard drive installed or not have a
hard drive installed.
IMPORTANT: If the drive bay is missing or not fully populated, the system will not meet the
thermal cooling requirements of the processor, which will most likely result in degraded
performance as a result of throttling or thermal shutdown of the system. It is recommended to
apply the air block on the blank HDD carrier if the installed HDD quantity is less than
four pieces.