Eltako ER12-002-8..230V UC 22002601 プリント

製品コード
22002601
ページ / 1
GB
Switching relays
ER12-001-8..230 V UC,
ER12-002-8..230 V UC
ER12-001:
1 change over contact potential free
16 A/250 V AC.
Safe disconnection to VDE 0106, Part 101;
therefore, these devices can also be used as
coupling relays.
ER12-002:
2 change over contacts potential free
16 A/250 V AC.
Incandescent lamp load up to 2000 W. 
No standby loss.
Modular device for DIN-EN 60715 TH35 
rail mounting.
1 module = 18 mm wide, 58 mm deep.
State-of-the-art hybrid technology combines
advantages of nonwearing electronic control
with high capacity of special relays.
Universal control voltage 8 to 230 V UC.
Low switching noise. Contact position 
indicator with LED. 
Integrated free-wheeling anti-surge diode
(A1= +, A2 = -).
By using a bistable relay coil power loss 
and heating is avoided even in the on mode.
The relay contact can be open or closed
when putting into operation. It will be 
synchronised at first operation.
Typical connections
ER12-001
22 001 601 - 1 
.
22 002 601 - 1
ER12-002
Technical Data
Control voltage
8..230 V UC
Rated switching capacity
16 A /250V AC
Incandescent lamp load and
2000 W
halogen lamp load
1)
230 V
Fluorescent lamp load with KVG
1000 VA
in lead-lag circuit or non compensated 
Fluorescent lamps with KVG
500 VA
shunt-compensated or wih EVG
Compact fluorescent lamp with
I on <
_ 70 A /
EVG and energy saving lamps
10 ms
2)
Standby loss (activ power)
_
1)
For lamps with 150 W max
2)
For electronic ballast gears a 40fold inrush
current has to be calculated. For steady loads of 
1200 W use the current-limiting relay SBR12.
The strain relief clamps of the 
terminals must be closed, that 
means the screws must be tightened
for testing the function of the device.
The terminals are open ex works.
Warning !
Only a trained electrician may install this
equipment, otherwise there is a risk of fire 
or electric shock.
01/2009 Specifications subject to change.
!