5-6        Connect Each Device to the Network
EtherNet/IP to DeviceNet Linking Device 1788-EN2DN
Set the DeviceNet Address
Disable AutoBaud
By default, AutoBaud is enabled for the linking device. If you use the 
linking device as the scanner for the DeviceNet network, disable 
AutoBaud for the linking device. The network requires at least one 
device with a fixed baud rate, which typically is the scanner.
The 1788-EN2DN device has no hardware mechanism to set its DeviceNet address.
1. Connect the device to the network.
2. Turn on the power to the device.
3. Use RSNetWorx software to set the address of the device. See Set an Address with 
4. After the device resets, check the DeviceNet network status indicator:
If:
Then the:
green (flashing or solid)
address is OK
solid red
address and/or baud rate conflict with another device
3. Go online to your DeviceNet network.
1. Start RSNetWorx software.
2. Open a new DeviceNet configuration file.
Go Online to Your DeviceNet Network