AEG PROTECT 1.11 ユーザーズマニュアル

ページ / 61
36
If  the  battery  cubicle  is  used  in  connection  with  the 
PROTECT 1.1.50  or  PROTECT  1.200,  the  strain  relief  is 
implemented with clamps.
The  battery  system  can  now  be  activated.  To  do  this,  insert 
the two fuses  . 
As the last step, fasten each cover that was initially removed.
Fig.: PROTECT 1.BP20 in connection with the PROTECT 1.100
i
PROTECT  1.100  &  1.BP20:  When  connecting 
the battery connection cable, make sure that the 
plugs  are  inserted  quickly  and  firmly  in  the 
battery connectors.
Prepare  further  PROTECT  1.BP20  battery  cubicles  as 
described  above  and  then  connect  them  to  the  terminals 
(X2 and X3) of the previously installed battery cubicle with the 
enclosed  battery  connection  cables.  Observe  the  correct 
polarity "+" and "-" as well as an earth-fault- and short-circuit-
proof routing during connection.
5.6
Mechanical Blocking of PROTECT 1.
After  completing  the  connection  work,  fasten  the  connection 
terminal  cover  again.  At  the  final  installation  site,  block  the 
cubicles against slipping.