The inverter is switched off if the battery voltage drops below 
a factory-set minimum voltage value. 
Never  store  the  unit  in  this  condition! The  discharged  battery 
system should be recharged within a week at the latest.
When  the  voltage  and  frequency  are  within  the  tolerance 
range  again  after  the  mains  is  restored,  the  rectifiers  switch 
back on automatically. The supply  of the inverter through the 
mains  is  resumed  and  the  battery  charger  charges  the 
battery. 
The  bar  graph  LED  (LED  chain  above  the  pictograph) 
indicates the remaining  battery capacity during this operating 
mode (see chapter 8, p. 45). 
6.1.3
Bypass Operation
Battery
Load 
REC
REC
INV
Manual 
bypass
Manual bypass path
SBS
Mains input 
miniature circuit 
breaker
Mains
Schematic 
diagram
Secured 
busbar
Load
Power circuit with 
faulty INV
 
If the inverter is overloaded or if overtemperature is detected, 
e.g.  also  if  an  inverter  defect  is  detected,  voltage  is  supplied 
to  the  load  without  interruption  via  the  static  bypass  switch 
(SBS) that switches on automatically. This is signalled by the 
Bypass LED.