AMC pm-scc-80 am ユーザーズマニュアル
1-1
Chapter 1 Installation
1.1 Loads Requirement
The Premium MPPT Series plays a major role in planning your PV system. The first
step in planning an efficient PV system is to calculate the load requirement. In order
to calculate the anticipated load requirement, it is important to determine average and
peak load consumption. The possible load growth should also be taken into
consideration when planning the load requirement because loads hardly remain static
and they grow more frequently than they reduce.
1.2 Battery Voltage System
After the estimate of the power requirement, the required power from the battery will
be the next consideration in planning the system. According to the basic rule of the
electricity, “Current is the power divided by voltage”, when the power amount
increases, it is suggested to raise the battery voltage so the current amount will
decrease. The principle is based on the larger amount of current is, the more expensive
the circuit protection is. In an example of the 96 watt load, it draws 4 amps at 24V
battery system but it draws only 2 amps at 48V system.
1.3 PV Array Voltage
As the Premium MPPT Series is a smart DC to DC converter design, the specification
of a PV array is much like sizing a grid tie inverter. Installers choose the max. and min.
Vmp and Voc of each string and how many strings are needed.
1.4 Maximum Voc
The maximum operating voltage of the PM-SCC-50AM and PM-SCC-80AM is 140
Vdc and of the PM-SCC-40AMW and PM-SCC-80AMW is 240Vdc. The protection
will be active to shut down the unit when the operating voltage is higher. PV array
manufacturers has the published data sheet with rated voltage and current as well as
the current and temperature coefficients. The rated Voc is measured in the temperature
of 25℃ so when calculated at lower temperature such as 0℃, 25% increase of the
rated Voc is expected. At different temperature location of installation, the maximum
Voc of the module should be determined by the Voc voltage temperature coefficient
and after that, a series string voltage may be determined as well.