HP proliant dl380 ユーザーズマニュアル

ページ / 50
HP 1200W Power Supply
Part Number - AC
500172-B21
Operational Input Voltage
Range (Vrms)
100 to 240
Frequency Range (Nominal)
(Hz)
50/60
Nominal Input Voltage (Vrms)
100
120
208
200
220
230
240
Maximum Rated Output Wattage
800
900
1200
1200
1200
1200
1200
Nominal Input Current (A rms)
9.7
9.0
7.0
6.8
6.4
9.1
5.9
Max Rated Input Wattage Rating
(Watts)
930
1034
1348
1348
1348
1348
1348
Max. Rated VA (Volt-Amp)
970
1079
1406
1406
1406
1406
1406
Efficiency (%) at Max. Rated
Output Wattage
86
87
89
89
89
89
89
Power Factor
0.97
0.97
0.97
0.97
0.97
0.97
0.97
Leakage Current (mA)
0.42
0.50
0.83
0.87
0.92
0.96
1.00
Max. Inrush Current (A peak)
30
30
30
30
30
30
30
Max. Inrush Current duration
(mS)
20
20
20
20
20
20
20
Maximum British Thermal Unit
Rating (BTU-Hr)
3174
3530
4600
4600
4600
4600
4600
 
HP 1200W PSU 48VDC Input Part Number
437573-B21
Input Voltage Range (DCV)
36-72
Frequency Range (Nominal) (Hz)
DC
Nominal Input Voltage (VDC)
36
48
72
Maximum Rated Output Wattage
1200
1200
1200
Nominal Input Current (ACD)
38
28
19
Max Rated Input Wattage Rating (Watts)
1380
1350
1365
Max. Rated VA (Volt-Amp)
1380
1350
1365
Efficiency (%) at Max. Rated Output Wattage
87
89
88
Power Factor
N/A
N/A
N/A
Leakage Current (mA)
N/A
N/A
N/A
Max. Inrush Current (A peak)
20
25
35
Max. Inrush Current duration (mS)
1
1
3
Maximum British Thermal Unit Rating (BTU-Hr)
4713
4610
4662
 
NOTES: To review typical system power ratings use the HP Power Advisor which is available online located at url:
QuickSpecs
HP ProLiant DL380 Generation 6
Power Specifications
DA - 13234   Worldwide QuickSpecs — Version 16 — 8.28.2009
Page 46