Optimum environment 
When installing the server in a rack, select a location that meets the 
environmental standards described in this section. 
 
Space and airflow requirements 
To allow for servicing and adequate airflow, observe the following space and 
airflow requirements when deciding where to install a rack: 
•  Leave a minimum clearance of 122 cm (48 in) in front of the rack. 
•  Leave a minimum clearance of 76.2 cm (30 in) behind the rack. 
•  Leave a minimum clearance of 122 cm (48 in) from the back of the rack to 
the back of another rack when racks are back-to-back. 
HP servers draw in cool air through the front door and expel warm air through 
the rear door. Therefore, the front and rear rack doors must be adequately 
ventilated to allow ambient room air to enter the cabinet, and the rear door must 
be adequately ventilated to allow the warm air to escape from the cabinet. 
  CAUTION:  To prevent improper cooling and damage to the 
equipment, do not block the ventilation openings. 
When vertical space in the rack is not filled by a server or rack component, the 
gaps between the components cause changes in airflow through the rack and 
across the servers. Cover all gaps with blanking panels to maintain proper 
airflow.