Individual parameters can be adjusted by the user. 
 
 
• Press the MANUAL button.  ① 
• It will display like the diagram to the right. 
• Press INITIALIZE first.  ② 
 
 
• Pressing MEASURE BODE carries out the frequency 
response measurement, and displays the waveforms. 
• By changing the GAIN [dB] value and measuring the 
frequency response, the Gain waveform will move up 
and down according to the GAIN value. 
• By changing the Q value and measuring the 
frequency response, the Phase waveform will move 
up and down according to the Q value. 
• Adjust so that the gray waveform and black waveform 
overlap. 
 
 
• Pressing MEASURE STEP carries out the step 
response measurement, and displays the step 
waveforms.   
• Change the FFGain and Overshoot values, measure 
the step response, and adjust so that the gray 
waveform and black waveform overlap. 
 
 
• Starting with HiSpeed Serial makes it possible to 
adjust individual parameters while operating 
high-speed serial communications.   
 
• Save the tuning results to EEPROM.    Refer to 9.4. Writing Parameters into ROM.