Disconnect and Connect DC Power
M40 Internet Router Hardware Guide
150
Figure 64:  Power Switch on a DC Power Supply in the OFF Position
5.
If the protective shield is installed over the power supply terminals, use a Phillips 
screwdriver to loosen and remove the screws that secure the shield to the power supply 
(see Figure 65).
Figure 65:  Remove the Protective Shield from the Terminal Studs
6.
Slide the power cable lugs onto the terminal studs on the power supply faceplate (see 
Figure 66):
„ Connect the positive (+) source cable lug to the return terminal, which is labeled 
RTN
.
„ Connect the negative (–) source cable lug to the input terminal, which is labeled 
–48V
.
Run the power cables to the left on the left power supply, and to the right on the right 
power supply. This arrangement enables you to replace a power supply without having 
to detach the cables from the other power supply.   
.
1128a
Power switch
.
Protective shield
Washer
1130
There is no standard color coding for DC power cables. The 
color coding used by the external DC power source at your 
site determines the color coding for the leads on the power 
cables that attach to the circuit breaker box. You must 
ensure that the connections at the circuit breaker box 
maintain the proper polarity. The power source DC cables 
might be labeled 
(+)
 and 
(–)
 to indicate their polarity.