Juniper CBL-M40-PWR-AU ユーザーズマニュアル

ページ / 268
Power System Requirements and Specifications
M40 Internet Router Hardware Guide
48
System Power Requirements
Table 14 lists the power requirements for the individual hardware components. The values in 
this table are listed under typical voltage conditions. The power requirements are the same 
for both the DC and AC power supplies.
Table 14:  System Power Requirements 
The numbers listed in Table 14 are fairly accurate for larger, typical configurations. When the 
total power consumption is calculated to be less than 600 watts, you should increase the 
number by 10 percent because the efficiency of the power supply is lower when supplying 
less current. The 10 percent reduction at lower power levels is an approximation. The actual 
reduction in efficiency is nonlinear and depends on the particular mix of PICs.
Do not substitute a metric nut driver or wrench for the 
7/16-in. nut driver or wrench needed to tighten and loosen 
the nuts on the terminal studs. A tool that does not fit the 
nuts exactly can damage them. If a 7/16-in. tool is not 
available, use pliers or an adjustable wrench.
Component
Power (Watts)
Base system (all items except the FPCs and PICs, with the fans running in normal 
mode
287 
(approximate)
Fans at full speed (additional power consumed when all the fans are running at their 
maximum)
144 
(approximate)
FPC
23.7
Because of variation in components, temperature, and 
supply voltage, we recommend you provision at least 35A 
@ 48V DC for a DC-powered router, or 8A @ 208V AC for 
an AC-powered router. This allows you to operate the 
router in any configuration without upgrading the power 
infrastructure.