Toshiba 1000 ユーザーズマニュアル

ページ / 64
 
 
 
19 
6.2 
Dry Contact Interface (optional card) 
 
 
 
 
Pin # 
Description 
I/O Type 
UPS fail, relay contact, normally open, active close. 
 output 
Summary alarm, relay contact, normally open, active close. 
One of the following signals activate this signal: 
1) Output fault 
2) Bus fault 
3) Over temperature 
4) Overload 
5) Over Charging 
6) Battery test fail 
7) Charger failure 
output 
GND for secondary 
 
Remote shutdown 
• Short Pin 4 & Pin 5: Remote Output Shutdown      
• Remove short between Pin 4 & Pin 5: UPS switch back 
to Inverter/Run 
input 
Common 
 
Bypass active, normally open, active close 
output 
Battery low, normally open, active close 
output 
No connection 
input 
Utility fail, normally open, active close (Requires 2 seconds 
for pin to activate) 
output 
Note:  Vcc Voltage is 9-12 Vdc. 
Table 2 : DryContact Pin Out Signal Chart 
 
DB9 Male Connector Outline 
(facing connector)