Aprilaire dehumidifier 1700 ユーザーズマニュアル
14
TROUBLESHOOTING GUIDE
SYMPTOM
TROUBLESHOOTING PROCEDURE / POSSIBLE REASON
Dehumidifier is not
draining properly.
draining properly.
• Check condensate trap to be sure it is clear.
• Check drain line for continuous slope.
Dehumidifier is producing
hot air.
hot air.
• Reheat of outgoing air will cause a temperature increase across the dehumidifier.
• Unit will possibly run continuously initially. After unit has “dried” home,
dehumidifier will cycle, reducing load.
HVAC fan does not turn
on when cycle time dial is
in “TEST” mode.
on when cycle time dial is
in “TEST” mode.
• Make sure there is power to the HVAC equipment.
• Check the wiring diagram for the R, C, W, Y, GH, and GS at the HVAC equipment,
thermostat, and the dehumidifier.
• Make sure the sensor is connected to the Outdoor Temperature Sensor terminals
or the System Setup block is set to “TIMED” mode.
• Check the voltage across the R and C terminals at the dehumidifier. Voltage
should be 18 VAC minimum - 30 VAC maximum.
• In “TEST” Mode, the HVAC fan will activate for 1 minute, DO NOT LEAVE IN TEST
MODE AS DEHUMIDIFIER WILL NOT OPERATE.
Dehumidifier Blower is running,
but no airflow.
but no airflow.
• Normally Open Damper was used instead of Normally Closed Damper in backflow.
• Total HVAC system static is higher than 0.8” w.c.
Dehumidifier not adequately
dehumidifying.
dehumidifying.
• Unit will need time to “dry” materials in home before effectively changing RH.
• Too little airflow through dehumidifier.
• Total HVAC system static is higher than 0.8” w.c.
• Compressor is not turning on.
• System undercharged.
The dehumidifier damper does
not open in “TEST” Mode.
not open in “TEST” Mode.
• Follow all of the system checkout procedures.
• Check the wiring diagram for the damper and 24 VAC transformers.
Fan cycling operates
continuously after the dial
is taken off “TEST” mode.
continuously after the dial
is taken off “TEST” mode.
• If the HVAC equipment is making a Heat or Cool call, or the fan is in Continuous
Operation, fan cycling will remain on until the requirement set by the cycle
period dip switch and knob is met.
period dip switch and knob is met.
• If the interval is set at 1 HOUR and the cycle time is set at 60 minutes, fan
cycling will be on continuously. Change the setting to a lower amount if this is
not desired.
not desired.