BEFORE BEGINNING INSTALLATION OF THIS PRODUCT
Disconnect all electrical power to the machine
Make sure the machine cannot operate during installation
Follow all safety warnings of the machine manufacturer
Read and follow all installation instructions
WARNING
General 
The Keystart 9620 series provides manual start/stop and automatic 
fault shutdown protection for generators, pumps and other engine-
driven applications. 
Keystart features a 3 way keyswitch for operator control of the engine, 
with 6 LEDs for indication of status and faults - see ‘front view’ diagram 
for details. Electrical connection and configuration options are at the rear 
- see ‘Rear view, connection and settings’ diagram. 
For each Keystart ordered, the following is supplied: 
• 
1 x Keystart module, fitted with 2 x panel mounting clips 
• 
2 x keys 
• 
these instructions 
Panel installation 
Keystart is designed for front-of-panel mounting in a DIN standard  
92 x 92 mm (3.6 x 3.6 in.) cut-out. Allow 75mm (3.0 in.) behind the 
panel for the case depth, keyswitch and cable connection. 
Secure the case to the panel with the two ratcheted mounting clips: 
1. 2. 
3. 
Remove the plastic 
mounting clips from 
the Keystart case: 
release each clip’s 
ratchet mechanism by 
pulling outwards (A), 
then slide the clip 
back and off the  
case (B).
 
At the front of the 
panel, insert the 
Keystart (without 
clips) into the panel 
cut-out (C).
 
At the rear of the panel, 
refit the two mounting 
clips into the slots on  
the Keystart case (D). 
Slide each clip forward 
until the arms (E) are 
secured behind the 
panel face. Ratchet 
mechanism (F) prevents 
the clip from moving 
backwards.
 
 
 
Keystart 9620 series 
Engine & Generator Controls
 
Installation Instructions 
00-02-0657
revision A, 22
nd
 September 2008
catalogue section 40 & 75
Please read the following information before installing. A visual inspection of this product for damage during 
shipping is recommended before installation. It is your responsibility to ensure that qualified mechanical and electrical 
technicians install this product. If in doubt, please contact your local Murphy representative. 
GENERAL INFORMATION
 
Product specifications  
power supply: 
 
 
operating voltage:   
   steady state 
   brown out / cranking 
 
7 – 30 VDC 
5 VDC 
current consumption 
< 100mA 
inputs: 
 
fault switch inputs: 
close to negative DC during fault 
–ve input defined as: 
–1V to +1V w.r.t. – ve DC supply 
speed sensing input: 
  generator AC (J2+J3 on) 
 
  mag. pickup (J2+J3 off) 
 
(model 9621 only) 
70 – 270 VAC rms,  
<50 to >60 Hz. nominal 
10 – 60 VAC peak,  
<2000 to >6500 Hz. nominal 
outputs: 
(all ratings non-reactive) 
run, preheat 
positive DC, switched NO relay contact,
10 A max. @ 24VDC 
start (crank) 
positive DC via keyswitch contacts, 
10 A max. @ 24V DC 
alarm 
negative DC (open collector  
NPN transistor), 250mA max. 
calibration/tacho 
to suit 0 – 1 mA, 75 Ohm meter 
output = 0.75mA at rated engine speed 
adjustable settings: 
 
preheat timer 
0 or 10 secs (link J1),  
default = 0 secs 
fault override timer 
2 to 20 secs (VR1),  
default = 10 secs 
overspeed trip level 
100 to 130 % (VR3) of  
nominal speed calibration (VR2),  
default = 110% (of 50 or 60 Hz) 
general: 
 
overall dimensions (w x h x d)  
96 x 96 x 95 mm / 3.8 x 3.8 x 3.7 in. 
panel cut-out size 
DIN 92 x 92 mm / 3.6 x 3.6 in. 
weight 
approx. 300 g / 0.7 lb 
operating temperature  
–35°C to +55°C / –31°F to 131°F 
Model options