MGE UPS Systems comet ex 11 rt 3-1 ユーザーズマニュアル

ページ / 38
 
34007724EN/AA
 - Page 33
BY
PASS
NORMAL
4.3 Hot-swapping the battery module
Disconnecting the battery module
 Switch the battery circuit breaker(s)  12  to the "0" position.
 Disconnect the battery cables  28  and  29  from the power module.
The battery module can be replaced. The connected equipment is
powered by the UPS.
It is also possible to replace battery trays instead of battery module.
Contact your nearest after sales support service.
To remove battery trays:
 First, switch the battery circuit breaker(s) to the "0" position.
 See section 2.3 and follow instructions to remove battery trays.
12
28
29
Reconnecting the battery module
 Reconnect the battery cables  28  and  29  to the power module.
 Switch the battery circuit breaker(s)  12  to the "I" position.
To reconnect battery trays:
See section 2.3 and follow the reverse instructions.
 When battery module front panel is closed, connect the battery cables
28  and  29  to the power module.
 Switch the battery circuit breaker(s)  12  to the "I" position.
29
28
Reconnecting the power module
 Secure the Input/Output junction box using the three screws.
 Reconnect the battery cables  28  and  29  to the power module.
 Switch the battery circuit breaker(s)  12  to the "I" position.
 Switch the Normal AC source circuit-breaker   9   to the "I" position.
 Turn the manual bypass switch from the BYPASS to the NORMAL
position.
 Check that the led  15  is on.
 Follow initial start up sequence (see section 3.1) in order to personalize
the UPS.
 Push the ON button  21  for more than 3 seconds.
The green led  13  is on, and the connected equipment is now
protected by the UPS.
15
OFF
ON
13
21
4. Maintenance
LOAD LEVEL
4 kW / 5 kVA