CLT- & CLX-1DIM4 
Functional Summary 
The Crestron
 1-Feed, 4-Dimmer Terminal Block and 
Module (CLT-1DIM4 and CLX-1DIM4, respectively), 
are considered a single entity and must be used together. 
They ship separately to permit termination of the field 
wiring to the CLT-1DIM4 prior to installation of the 
CLX-1DIM4, as described in this guide. They can be 
mounted in any Crestron Automation Enclosure (CAEN-
Series Enclosures). The terminal block is designed to 
terminate the circuit feed (LINE and NEUTRAL) and 
distribute the controlled circuit (LOAD) to the fixtures. 
The module connects to the terminal block and performs 
dimming control of four incandescent, magnetic low 
voltage, neon, cold cathode, or dimmable 2-wire 
fluorescent lighting loads. The maximum load is 16 amps 
for any controlled circuit, limited to 16 amps total per 
module. The unit requires 120VAC 60 Hz, 1 phase input 
voltage. An oversize heat sink dissipates heat efficiently. 
There are LEDs on the module to indicate communication 
to a Cresnet
 network, input power to the module, and 
output power to the load. 
NOTE:  When connecting to an Arc Fault Breaker, the 
load should not exceed 1000 watts total.  
Industry Compliance 
This product is Listed to applicable UL Standards and 
requirements by Underwriters Laboratories Inc. 
     
(E103692)
 
Installation 
Terminal block and module must be mounted into a 
Crestron Automation Enclosure by a licensed electrician, 
in accordance with all national and local codes.  
CAUTION:  This equipment is for indoor use only and 
needs to be air-cooled. Mount in a well-ventilated area. 
The ambient temperature must be 32
°F to 104°F (0°C to 
40
°C). The relative humidity must be 0% to 90% (non-
condensing).  
Terminal blocks are installed along the left side of single-
wide enclosures and along the outside edges (left and 
right sides) of double-wide enclosures. Modules are 
installed along the right side of single-wide enclosures 
and side-by-side in the center of double-wide enclosures. 
When installing modules and terminal blocks in a double-
wide enclosure, be sure to invert units on the right side so 
that they can be properly wired. Refer to the illustrations 
shown below when considering the location of terminal 
blocks and modules within an enclosure.  
NOTE:  Modules and terminal blocks must be installed 
into the lowest available spaces and continue toward the 
top of the enclosure. 
Terminal Block & Module Locations (Single-wide Enclosure) 
N OUT 4
N OUT 3
N OUT 2
N OUT 1
1 FEED
120VAC 60 Hz
16A MAX
CLX-1DIM4
GROUNDING
TERMINAL
BLOCK
DIM 4
DIM 3
DIM 1
DIM 2
4 DIM
LINE
TERMINAL
BLOCK
N IN
MODULE
 
 
Terminal Block & Module Locations (Double-wide Enclosure) 
TERMINAL BLOCK
(RIGHT)
N OUT 4
GROUNDING TERMINAL BLOCKS
TERMINAL BLOCK
(LEFT)
N OUT 3
N OUT 2
N IN
N OUT 1
DIM 4
DIM 3
DIM 1
DIM 2
LINE
1 FEED
120VAC 60 Hz
16A MAX
4 DIM
CLX-1DIM4
MODULE
N OUT 4
N OUT 3
N OUT 2
N OUT 1
N IN
DIM 4
DIM 3
DIM 2
DIM 1
LINE
CLX-1DIM4
120VAC 60 Hz
16A MAX
1 FEED
4 DIM
 