GENERATOR START-UP PROCEDURE 
BEFORE STARTING 
1. Place 
the 
main, G.F.C.I., and aux. circuit breakers (Figure 
36) in the OFF position prior to starting the engine.
Figure 36.  Main, Aux. and GFCI 
Circuit Breakers (OFF)
2.  Make sure the voltage change-over board has been 
confi gured for the desired output voltage.
3.  Connect the load to the receptacles or the output 
terminal lugs as shown in Figure 11. These load 
connection points can be found on the output terminal 
panel and the output terminal panel’s hard wire hookup 
panel. 
4.  Tighten terminal nuts securely to prevent load wires 
from slipping out.
5.  Close all engine enclosure doors (Figure 37).
Figure 37.  Engine Enclosure Doors
  CAUTION
The engine’s exhaust contains harmful emissions. 
ALWAYS have adequate ventilation when operating. 
Direct exhaust away from nearby personnel.
  WARNING
NEVER manually start the engine with the main, GFCI 
or auxiliary
 circuit breakers in the ON (closed) position.
INCORRECT
CORRECT
STARTING
1. Place 
the voltage selector switch in the desired 
voltage position (Figure 38)..
Figure 38.  Voltage Selector Switch
STARTING (MANUAL)
1.  In warm weather conditions, skip to step 3. In cold 
weather conditions, preheat the engine glow plugs by 
turning the ignition key (Figure 39) to the RUN 
position..
Figure 39.  Ignition Switch Pre-Heat
(Run Position)
2.  Depending on the temperature of the coolant (cold 
weather conditions), the pre-heat lamp (Figure 40) will 
light (ON) and remain on until the pre-heating cycle has 
been completed. After completion of the pre-heating 
cycle, the light will go OFF and the engine will start up 
automatically.
Figure 40.  Pre-Heat Lamp