Unity 4600 User’s Manual 
4.
Press ESC to return to the DTMF Setup screen or ESC to return to the Installation Testing 
screen.
Relay Pulse 
Check
This test may be used to verify connections to the alarm or cue relays. Each relay, as it is 
tested, will energize and de-energize about once per second. Use the following steps to 
check these connections:
1.
First, verify that each relay is set either to ON or OFF. Relays placed in the nonvolatile 
"Follow Warning" setting will not respond to the Pulse command used in this test.
2.
From the DTMF Level Set screen, press the right-arrow button to display the Relay Pulse 
Check screen.
3.
Press 
ENT
 to display the Relay 1 Check screen.
4.
The Relay Check screen will indicate that the relay is On or Off as it switches on and off 
about once per second. At the same time, a user should see the ohm-meter reading 
between the output contacts alternate between zero and (virtually) infinite.
5.
Press the right-arrow button to test the remaining cue relays and the alarm relay.
6.
Press 
ESC
 to return to the Relay Check screen.