Mitsubishi Electronics MELSEC FX2N ユーザーズマニュアル

ページ / 70
FX2N-32DP-IF Profibus-DP Interface Unit
Introduction 1
1-8
1.3.3
Configuration Rules
1) Special function blocks: Max. 8 blocks per 32DP-IF.
Check the loading on the 5 V DC bus supply. Consumption values for special function
blocks can be found in Table 1.7. For maximum available current see the Table 1.6. 
2) Maximum I/O points: 256 or less. 
3) Check the loading on the 24 V DC service supply. Look up the number of expansion I/O in
Figure 1.4. Find the residual current. This can then be used to power sensors etc.
4) Check total exchanged data length in DP-master, this number might be limited by the DP-
master unit. Data length is exchanged between the 32DP-IF and a DP-master in every
cycle.
For the data length of connected extension units/blocks, refer to Table 1.3.
However, the maximum amount of data that can be exchanged with the 32DP-IF is 200 byte
inputs and 200 byte outputs. 
Figure 1.4: Number of Expansion I/O and 24 V DC Service Supply Capacity (mA)
For extension unit, refer to FX
2N
 Series Hardware Manual.
Table 1.6: 24 and 5 V DC Supply Capacity
Items
Power Supply
24 V DC Service Supply
500 mA at 24 V DC
Max. 5 V DC Bus Supply
220 mA at 5 V DC
Table 1.7: Power Supply for Special Function Blocks
Model
Description
Number of 
I/O Points
Power Supply
Internal 5 V DC 
(mA)
External 24 V DC 
(mA)
FX
2N
-4DA
Digital to analog converter
8
30
200
FX
2N
-4AD
Analog to digital converter
8
30
55
FX
2N
-4AD-PT
PT100 probe interface
8
30
50
FX
2N
-4AD-TC
Thermo-couple interface
8
30
50
Number of 
additional 
output 
(points)
> 32
32
200
150
100
50
0
Invalid configuration
24
275
225
175
125
75
25
16
350
300
250
200
150
100
50
0
8
425
375
325
275
225
175
125
75
25
0
500
450
400
350
300
250
200
150
100
0
8
16
24
32
40
48
56
64
> 64
Number of additional input (points)