Mitsubishi Electronics MELSEC FX2N ユーザーズマニュアル

ページ / 70
FX2N-32DP-IF Profibus-DP Interface Unit
Advanced Devices 4
4-4
4.2.1
32DP-IF Status (M8000 ~ M8009 and D8000 ~ D8009)
Figure 4.2: Momentary Power failures
Figure 4.3: 32DP-IF Version
Table 4.3: Special Auxiliary Relays (M8000 ~ M8009)
Diagnostic 
Device
Name
Description
M8000 
(
)
RUN LED monitor
ON when 32DP-IF is exchanging data with extension I/O 
blocks/units and special. This device operate same as RUN 
LED.
M8001 ~ M8003
Reserved
M8004 
(
)
(ref. D8004)
Error occurrence
ON when one or more error flags (M8060 to M8068) is ON. If 
this bit is ON, error number is written in D8004. 
M8005, M8006
Reserved
M8007 
(
) (
)
(ref. D8007)
Momentary 
power failure
See Figure 4.2.
M8008, M8009
Reserved
Table 4.4: Special Data Registers (D8000 ~ D8009)
Diagnostic 
Device
Name
Description
D8000
Reserved
D8001 
(
)
32DP-IF version
This value is 32DP-IF version code. See Figure 4.3.
D8002, D8003
Reserved
D8004 
(
) (
)
Error number 
M
The contents of this register 
 identifies which error flag 
is active, i.e. if 
 = 8061, identifies M8061
D8005, D8006
Reserved
D8007 
(
) (
)
Number of 
momentary 
power failures
This value is counted when M8007 is ON. This value is reset 
on full power OFF.
D8008 
(
)
Power failure 
detection period
Power failure detection period is 10 ms.
D8009
Reserved
AC Power
Exchanged
with DP-master
M8007
Momentary power failure
10 ms
5 ms
This time is power failure detection period.
Version No.: Ex. 100 = V1.00
Module Type No.: Ex. 20 = 32DP-IF
dec