Mitsubishi Electronics MELSEC FX2N ユーザーズマニュアル
FX2N-32DP-IF Profibus-DP Interface Unit
Advanced Devices 4
4-10
4.2.4
Error Status (M8060 ~ M8069 and D8060 ~ D8069)
Table 4.11:Special Auxiliary Relays (M8060 ~ M8069)
Diagnostic
Device
Name
Check Points
M8060
(
) (
)
(ref. D8060,
D8061)
D8061)
I/O configuration error
If this flag is ON, check error code in D8060,
D8061 and extension cable.
D8061 and extension cable.
M8061
(
) (
)
(ref. D8060,
D8061)
D8061)
32DP-IF hardware error
If this bit is ON, check error code in D8061.
M8062, M8063
Reserved
M8064
(
) (
)
(ref. D8064
Parameter error
If this flag is ON, check error code inD8064 and
DP-master setting.
DP-master setting.
M8065, M8066
Reserved
M8067
(
) (
)
(ref. D8067)
Operation error
If this flag is ON, check error code in D8067 and
D8068, DP-master parameter, and the extension
cable.
D8068, DP-master parameter, and the extension
cable.
M8068
(
)
(ref. D8068)
Parameter error and operation
error
error
If M8064 or M8067 is ON, this bit would be set to
ON. This bit is cleared by resetting the power
supply.
ON. This bit is cleared by resetting the power
supply.
M8069
Reserved