Mitsubishi Electronics MELSEC FX2N ユーザーズマニュアル

ページ / 70
FX2N-32DP-IF Profibus-DP Interface Unit
Advanced Devices 4
4-10
4.2.4
Error Status (M8060 ~ M8069 and D8060 ~ D8069)
Table 4.11:Special Auxiliary Relays (M8060 ~ M8069)
Diagnostic 
Device
Name
Check Points
M8060 
(
) (
)
(ref. D8060, 
D8061)
I/O configuration error
If this flag is ON, check error code in D8060, 
D8061 and extension cable.
M8061 
(
) (
)
(ref. D8060, 
D8061)
32DP-IF hardware error
If this bit is ON, check error code in D8061.
M8062, M8063
Reserved
M8064 
(
) (
)
(ref. D8064
Parameter error
If this flag is ON, check error code inD8064 and
DP-master setting.
M8065, M8066
Reserved
M8067 
(
) (
)
(ref. D8067)
Operation error
If this flag is ON, check error code in D8067 and 
D8068, DP-master parameter, and the extension 
cable.
M8068 
(
)
(ref. D8068)
Parameter error and operation 
error
If M8064 or M8067 is ON, this bit would be set to 
ON. This bit is cleared by resetting the power 
supply. 
M8069
Reserved