FX2N-32DP-IF Profibus-DP Interface Unit
User Parameter 6
6-4
6.2
Configuring Slave Parameter
Caution:
The user parameter data and configuration of the 32DP-IF must always be consistent. To
ensure that the user parameter data and the configuration of the 32DP-IF are matching
each other, the user parameter data set should always be constructed by using the GSD file
that has been delivered with the 32DP-IF.
ensure that the user parameter data and the configuration of the 32DP-IF are matching
each other, the user parameter data set should always be constructed by using the GSD file
that has been delivered with the 32DP-IF.
6.2.1
Configuring Slave Parameter by GSD file
The parameter setting of the 32DP-IF can be entirely defined using the GSD file that comes on
the disk together with 32DP-IF. For an easy adjustment of all user parameter data, the
Mitsubishi Profimap Software V2.X or a configuration software from another vendor which is
supporting extended parameter setting should be used.
the disk together with 32DP-IF. For an easy adjustment of all user parameter data, the
Mitsubishi Profimap Software V2.X or a configuration software from another vendor which is
supporting extended parameter setting should be used.
Note:
In configuring 32DP-IF GSD file, first assign special function blocks, second extension I/O
units/blocks’ input data, and finally extension I/O units/blocks’ output data. The physical
placement of the module does not have to correspond with the GSD file order.
units/blocks’ input data, and finally extension I/O units/blocks’ output data. The physical
placement of the module does not have to correspond with the GSD file order.
6.2.2
Configuring Slave Parameter by Programming Tool
The process of defining a parameter using the programming tool is shown in Figure 6.3.
Please only use a programming tool if configuring a single special function block. It is recom-
mended to utilize the functionality of the GSD file when configuring more than one. As it is
much easier to use for this purpose.
mended to utilize the functionality of the GSD file when configuring more than one. As it is
much easier to use for this purpose.
Caution:
Any mistake in changing D200 ~ D299 can lead to a different interptetation of the Profibus-
DP data, which can result in a malfunction of the connected I/O units/blocks and special
function blocks.
DP data, which can result in a malfunction of the connected I/O units/blocks and special
function blocks.
Figure 6.3: Process Making Parameter Data by Programming Tool
1. Input parameter data in D200 ~ D299.
2. Turning M8020 from OFF to ON, 32DP-IF send parameter
(D200 ~ D299) extention units/blocks. After this data
furnish to be sent, M8020 is reset automatically.
(D200 ~ D299) extention units/blocks. After this data
furnish to be sent, M8020 is reset automatically.
3. Setting end