Appendix A
A-1
Appendix A:
Default Parameter <After Power ON>
A-1
User Parameter <After Power ON>
Figure A-1:User Parameter <After Power ON>
*1 Type code of special function block is as following table. This code in the parameter must
be written first Lower byte and second higher byte 
*2 After power on, the default setting of this parameter for every special function block is 2.
User Parameter for 32DP-IF
Byte No.
0
1
Bit 0
Bit 1
Bit 2
Meaning
Reserved 
(must be 0)
Swap data flag
I/O block status is 
checked in every 
cycle: Y/N
Special function 
block’s BFM #29 
(Error status) is 
checked: Y/N.
Description
Default setting is 
OFF (0), byte data 
are not swapped 
within a word.
Default setting is 
OFF (0), the status 
check of the I/O 
units/blocks is not 
performed in every 
cycle.
Default setting is 
OFF (0), BFM #29 
of all connected 
special function 
blocks is not 
checked in every 
cycle.
User Parameter for First Special Function Block
Byte No.
3
4
5
6
Meaning
Type code of special 
function block, lower 
byte of BFM 30 
*1
Type code of special 
function block, 
higher byte of BFM 
30 
*1
Total length m of 
parameter data for 
this special function 
block. 
Contains n = 0, as 
BFM addresses will 
be assigned dynam-
ically 
*3
Description
m = 2 
*2
.....
User Parameter for Last (y 
*4
 th) Special Function Block
Byte No.
.....
2 + 4 
×
 (y 
*4
 - 1) + 1
....
2 + 4 
×
 y 
*4
Meaning
.....
Type code of special 
function block, lower 
byte of BFM 30 
*1
.....
Contains n = 0, as 
BFM addresses will 
be assigned dynam-
ically 
*3
Description
Table A-1: Type Code of Special Function Blocks
Type
BFM 30 Code Dec
BFM30 Code Hex
FX
2N
-4AD
K2010
07DA Hex
FX
2N
-4AD-TC
K2030
07EE Hex
FX
2N
-4AD-PT
K2040
07F8 Hex
FX
2N
-4DA
K3020
0BCC Hex
FX2N-32DP-IF Profibus Interface unit