Tecnoware FGCEVODS15TT/00 プリント

ページ / 2
UPS 
Three-Phase
Industry
I
UPS EVO DSP TT 
from 10 to 100 KVA
State of the Art Technology
Specification
UPS EVO DSP MODEL
10.0 TT
15.0 TT 
20.0 TT 
30.0 TT
40.0 TT
60.0 TT 
80.0 TT 
100.0 TT
Output power ( KVA ) 
10
15
20
30
40
60
80
100
Nominal Active Power ( KW ) 
8
12
 16 
24
32
48
64
80
Power factor
0.8
Technology
On-Line Double Conversion transformerless (VFI-SS-111)
UPS Dimension LxHxP ( Cm )
40x107x78
52x130x90
52x130x95
64x140x98
Dimension with pack LxHxP ( Cm )
48x122x81
60x145x95
60x145x100
72x155x103
INPUT
Number of phases
3Ph+N
Nominal Voltage
380V/400V/415V
Input Voltage range ( L-N ) 
187Vac-280Vac at 100% load, 120Vac-280Vac at 64% load, 80Vac-280Vac at 42% load
Nominal Frequency ( Hz )
50/60
Frequency range for online operation 
±10%
Input Current THD 
   3%
Input Power Factor
0.99
OUTPUT
 
Number of phases
3Ph+N
Voltage
380V/400V/415V
Static Voltage Regulation at %100
<1%
Linear Load ( online&battery mode )
Voltage THD at rated linear load
<3%
Crest factor
3:1
Frequency (Hz)
50/60
Free Running Frequency (Hz) 
± 0.01%
Overload
125% for 10 minutes
150% for 1 minute
On Line Efficiency 
  92%
Eco Mode Efficiency 
  99%
BYPASS
 
Number of phases
3Ph+N
Voltage Range for bypass operation
220V / 230V / 240V (F-N) ± 10%
Frequency Range for bypass operation (Hz)
47-53 ( Configurable )
BATTERY
 
Type
Lead Acid, Sealed Maintenance Free
Battery Quantity (pcs ) 
62 ( 2x31 )
Battery Charger Time (Typical)
6-8 hours
Battery Test
Standard (Automatic and manual)
COMMUNICATION
 
Interface (Communication Ports )
RS232 e RS422
Dry Contact Signals
AC failure, Battery under voltage, bypass operation, output failure
EPO
Yes
Generetor Interface
Yes
Software 
Generex UPS Management - Optional
(Compatible with OS WINDOWS, UNIX, LINUX, MAC OS X, SUN SOLARIS)
Interfaccia SNMP
Generex SNMP Kit - Optional
(SNMP internal module CS121BSC, Software RCCMD
Compatible with OS WINDOWS, UNIX, LINUX, MAC OS X, SUN SOLARIS)
PARALLEL CONFIGRATION
Redundant parallel system
Up to 4 unit
GALVANIC ISOLATION
Isolation trasformer
Optional
ENVIRONMENTAL CONDITIONS
Storage Temperature Range (°C )
-25 to +55 ( 15 to 40 recomended for longer battery life time )
Operating Temperature Range (°C )
0 to 40 ( 20 to 25 recomended for longer battery life time )
Relative Humidity Range
0-95% ( non-condensing )
Maximum Altitude without derating (m)
1000
Protection Level
IP20
Certifications
CE ( Standards: IEC EN 62040-1 security; EMC IEC EN 62040-2; IEC EN 62040-3 classification )
Warranty
 
Validity
1 year