Honeywell 62-0342-01 ユーザーズマニュアル

ページ / 16
SUB SERIES INTERVAL DATA RECORDERS
62-0342—01
8
APPENDIX D - SYSTEM WIRING GUIDES
Fig. 12. Wiring overview for SUBIDR-8.
Note:  Meter 1 must be installed within 
100 feet of IDR. Meters 2-8 must be installed 
within 500 feet of IDR.
(Up to 8 Meters) 
(One of three channels shown for clarity.) 
(Up to 8 Meters) 
Channel 1 of 3 
4-Conductor 
Flat Modular Cable 
Up to 4000 Feet Total 
 
Daisy-Chain or  
Star Connection 
Up to 52 SUBIDR-8s per channel
AC Adapter 
SUB-RS232K
6' cable provided by
Honeywell
 (15 ft max.)
8-conductor cable
& modular plug
DB-9 (DTE) Connector 
PC
RJ-45 
RJ-11 
8-Cond. 
RJ-45 
RJ-11 
6-Cond. 
RJ-45 
6-Cond. 
RJ-45 
Wiring Guide for SUBIDR-8
IDR A 
IDR Z 
CONNECTION   CABLE 
TYPE  CONNECTOR
SUBIDR to Honeywell Meter #1 
8-cond. 22-26 AWG 
RJ-45
   flat 
modular 
cable
SUBIDR to Honeywell Meters #2-8 
6-cond. 22-26 AWG 
RJ-45
 
 
 
(Pins 1 & 8 not used)
SUBIDR to SUBIDR 
 
4-cond. 26 AWG 
RJ-11
SUBIDR to SUB-RS232K   
4-cond. 26 AWG 
RJ-11
SUB-RS232K to Computer * 
8-cond. 22-26 AWG 
RJ-45/DTE
   flat 
modular 
cable
SUB-RS232K to Modem *  
8-cond. 22-26 AWG 
RJ-45
   flat 
modular 
cable
SUBIDR to SUB-USBK *   
Allows connection directly
   to 
the 
computer 
USB
SUBIDR to Pulse Meter   
2-cond. 14-22 AWG
* Supplied by Honeywell
Note:  When constructing field-installed cables, modular cables must be made 
so that the individual wires go through on the same pin number.